| 2021-10-14 14:51:36 | ROOFING REVIEW: | | | | | | 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | | | A)HIP & RIDGE METAL SUPPORT TO BE USED. AND, CLEARLY | | | MARK SPECIFIC METAL CHANNEL TO BE INSTALLED. SEE | | | PERFORMANCE LIMITATIONS TABLES ON PRODUCT APPROVAL | | | SUBMITTED. | | | | | | B) ROOF UNDERLAYMENT FL14317-R12 SUBMITTED: CLEARLY | | | MARK WHICH TESTED ASSEMBLY IS GOING TO BE INSTALLED. | | | SEC. 5.8.2 AND SEC. 5.8.3 OF PRODUCT APPROVAL | | | SUBMITTED. | | | THERE ARE 6 ASSEMBLIES. SPECIFY WHICH ASSEMBLY FROM | | | SEC. 5.8.3.1 IS GOING TO BE INSTALLED. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|