Plan Review Notes
Plan Review Notes For Permit 21080730
Permit Number 21080730
Review Stop E
Sequence Number 1
Notes
Date Text
2021-09-27 13:38:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 220.16 LOADS FOR ADDITIONS TO EXISTING INSTALLATIONS.
  
 (A) DWELLING UNITS. LOADS ADDED TO AN EXISTING DWELLING
 UNIT(S) SHALL COMPLY WITH THE FOLLOWING AS APPLICABLE:
  
 (1) LOADS FOR STRUCTURAL ADDITIONS TO AN EXISTING
 DWELLING UNIT
 OR FOR A PREVIOUSLY UNWIRED PORTION OF AN EXISTING
 DWELLING
 UNIT, EITHER OF WHICH EXCEEDS 46.5 M2 (500 FT2), SHALL
 BE CALCULATED IN ACCORDANCE WITH 220.12 AND 220.14.