Plan Review Notes
Plan Review Notes For Permit 21080730
Permit Number 21080730
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-14 13:53:43RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080730
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 NOTE:
 SEC. 606 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE.
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 AND ENGINEER OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 SUBMIT DRAWINGS ELECTRONICALLY WITH
 ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE
 HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 2-LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807
 FBC-RESIDENTIAL.
  
 4- SPECIFY ROOF SHEATHING NAIL TYPE, SIZE AND SPACING
 AS REQUIRED BY SEC. R803.2 FBC-RESIDENTIAL.
 NOTE: ROOF SHEATHING ATTACHMENT DETAIL 1/S2 DOESN'T
 PROVIDE THIS INFORMATION.
  
 5-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)FRENCH DOOR AS SHOWN ON PLANS.
 NOTE: NOA FRENCH DOOR FL34006.4 UPLOADED TO PROJECTDOX
 SHOWS WINDOW MULLION PRODUCT APPROVAL NOT FRENCH DOOR.
  
 B)HIP & RIDGE METAL SUPPORT TO BE USED. AND, CLEARLY
 MARK SPECIFIC METAL CHANNEL TO BE INSTALLED. SEE
 PERFORMANCE LIMITATIONS TABLES ON PRODUCT APPROVAL
 SUBMITTED.
  
 C)ROOF UNDERLAYMENT FL14317-R12 SUBMITTED: CLEARLY MARK
 WHICH TESTED ASSEMBLY IS GOING TO BE INSTALLED. SEE
 SEC. 5.8.2 AND SEC. 5.8.3 OF PRODUCT APPROVAL
 SUBMITTED.
 THERE ARE 6 ASSEMBLIES. SPECIFY WHICH ASSEMBLY FROM
 SEC. 5.8.3.1 IS GOING TO BE INSTALLED.
  
 6- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT
 IS SPECIFYING R-20 ICYNENE SPRAY INSULATION. PROVIDE
 ICC EVALUATION REPORT FOR THE ICYNENE R-20 INSULATION
 TO VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 7- DETAIL 4/A-05 AND DETAIL 5 ON SHEET A-05: REVISE THE
 SIZE OF THE STRUCTURAL BUCK SPECIFIED. STRUCTURAL BUCK
 NEEDS TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AND
 NEED TO EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW
 OR DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL. 2X4 BUCK IS SMALLER THAN THE DOOR
 FRAME. REVISE AS REQUIRED.
  
 8-PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 AFIREWATER FIREPLACE. SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]