| 2021-10-14 13:53:43 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21080730 |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | NOTE: |
| | SEC. 606 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING |
| | BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE. |
| | |
| | 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT |
| | AND ENGINEER OF RECORD. ALL DRAWINGS NEED TO BE SIGNED |
| | AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER |
| | 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | SUBMIT DRAWINGS ELECTRONICALLY WITH |
| | ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE |
| | HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND |
| | SIGNATURE. |
| | |
| | 2-LOT DRAINAGE |
| | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | R401.3 FBC-RESIDENTIAL. |
| | SEC. 107.2.5 CITY AMENDMENTS. |
| | SEC. 110.9 CITY AMENDMENTS. |
| | |
| | 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- SPECIFY ROOF SHEATHING NAIL TYPE, SIZE AND SPACING |
| | AS REQUIRED BY SEC. R803.2 FBC-RESIDENTIAL. |
| | NOTE: ROOF SHEATHING ATTACHMENT DETAIL 1/S2 DOESN'T |
| | PROVIDE THIS INFORMATION. |
| | |
| | 5-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)FRENCH DOOR AS SHOWN ON PLANS. |
| | NOTE: NOA FRENCH DOOR FL34006.4 UPLOADED TO PROJECTDOX |
| | SHOWS WINDOW MULLION PRODUCT APPROVAL NOT FRENCH DOOR. |
| | |
| | B)HIP & RIDGE METAL SUPPORT TO BE USED. AND, CLEARLY |
| | MARK SPECIFIC METAL CHANNEL TO BE INSTALLED. SEE |
| | PERFORMANCE LIMITATIONS TABLES ON PRODUCT APPROVAL |
| | SUBMITTED. |
| | |
| | C)ROOF UNDERLAYMENT FL14317-R12 SUBMITTED: CLEARLY MARK |
| | WHICH TESTED ASSEMBLY IS GOING TO BE INSTALLED. SEE |
| | SEC. 5.8.2 AND SEC. 5.8.3 OF PRODUCT APPROVAL |
| | SUBMITTED. |
| | THERE ARE 6 ASSEMBLIES. SPECIFY WHICH ASSEMBLY FROM |
| | SEC. 5.8.3.1 IS GOING TO BE INSTALLED. |
| | |
| | 6- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT |
| | IS SPECIFYING R-20 ICYNENE SPRAY INSULATION. PROVIDE |
| | ICC EVALUATION REPORT FOR THE ICYNENE R-20 INSULATION |
| | TO VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 7- DETAIL 4/A-05 AND DETAIL 5 ON SHEET A-05: REVISE THE |
| | SIZE OF THE STRUCTURAL BUCK SPECIFIED. STRUCTURAL BUCK |
| | NEEDS TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AND |
| | NEED TO EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW |
| | OR DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| | FBC-RESIDENTIAL. 2X4 BUCK IS SMALLER THAN THE DOOR |
| | FRAME. REVISE AS REQUIRED. |
| | |
| | 8-PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW |
| | AFIREWATER FIREPLACE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |