Plan Review Notes
Plan Review Notes For Permit 21080720
Permit Number 21080720
Review Stop B
Sequence Number 3
Notes
Date Text
2021-10-13 16:18:05BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 2ND REVIEW COMMENTS
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. FBC R 301, IT APPEARS THE PROPOSED IMPROVEMENT IS
 OUTDOORS. HOW WILL THIS RESIST WIND LOADS?
  
 "FOUNDATION NOTES" STATE THIS IS EXPOSURE B, HAVE
 ENGINEER EXPLAIN RATIONALE FOR EXPOSURE B.
  
 2. FBC R 301, PLAN INCLUDES WIND DESIGN CRITERIA BUT
 LACKS STRUCTURAL DETAILS TO SHOW HOW THIS WILL RESIST
 WIND LOADS.
  
 3. SHEET 2 OF 3 MAKES REFERENCE TO A "GRILL CENTER",
 PROVIDE STRUCTURAL DETAILS. SPECS FOR THE GRILL AND
 PIZZA OVEN WERE PROVIDED BUT SHOW THEM INSTALLED INTO A
 FREESTANDING STRUCTURE, NO DETAILS PROVIDED FOR THE
 CABINETRY, NOT CLEAR HOW THE CABINETRY WILL RESIST WIND
 LOADS AS IT APPEARS THAT THE PROPOSED INSTALLATION IS
 NOT WITHIN THE BUILDING FOOTPRINT.
  
 4. SHEET 1 STILL HAS STEPHEN GAYDOSH'S TITLE BLOCK, SEE
 PREVIOUS LIST, HIS LICENSED IS REVOKED. FS471.
 (CORRECTED)
  
 NEW COMMENTS:
  
 5. THIS SITE APPEARS TO BE LOCATED IN EXPOSURE "C" PER
 FBC R301.2.1.4.2. DESIGNER SHALL PROVIDE RATIONAL
 ANALYSIS FOR USING EXPOSURE "B" FOR THE STRUCTURAL
 DESIGN.
  
 6. PROVIDE STRUCTURAL DETAILS. INCLUDE FOUNDATION TO
 WALL CONNECTION AND WALL VERTICAL RE-INFORCING. SPECIFY
 GROUT TO BE USED IN WALL CELLS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  