| 2021-10-13 16:18:05 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 3RD REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | |
| | 2ND REVIEW COMMENTS |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1. FBC R 301, IT APPEARS THE PROPOSED IMPROVEMENT IS |
| | OUTDOORS. HOW WILL THIS RESIST WIND LOADS? |
| | |
| | "FOUNDATION NOTES" STATE THIS IS EXPOSURE B, HAVE |
| | ENGINEER EXPLAIN RATIONALE FOR EXPOSURE B. |
| | |
| | 2. FBC R 301, PLAN INCLUDES WIND DESIGN CRITERIA BUT |
| | LACKS STRUCTURAL DETAILS TO SHOW HOW THIS WILL RESIST |
| | WIND LOADS. |
| | |
| | 3. SHEET 2 OF 3 MAKES REFERENCE TO A "GRILL CENTER", |
| | PROVIDE STRUCTURAL DETAILS. SPECS FOR THE GRILL AND |
| | PIZZA OVEN WERE PROVIDED BUT SHOW THEM INSTALLED INTO A |
| | FREESTANDING STRUCTURE, NO DETAILS PROVIDED FOR THE |
| | CABINETRY, NOT CLEAR HOW THE CABINETRY WILL RESIST WIND |
| | LOADS AS IT APPEARS THAT THE PROPOSED INSTALLATION IS |
| | NOT WITHIN THE BUILDING FOOTPRINT. |
| | |
| | 4. SHEET 1 STILL HAS STEPHEN GAYDOSH'S TITLE BLOCK, SEE |
| | PREVIOUS LIST, HIS LICENSED IS REVOKED. FS471. |
| | (CORRECTED) |
| | |
| | NEW COMMENTS: |
| | |
| | 5. THIS SITE APPEARS TO BE LOCATED IN EXPOSURE "C" PER |
| | FBC R301.2.1.4.2. DESIGNER SHALL PROVIDE RATIONAL |
| | ANALYSIS FOR USING EXPOSURE "B" FOR THE STRUCTURAL |
| | DESIGN. |
| | |
| | 6. PROVIDE STRUCTURAL DETAILS. INCLUDE FOUNDATION TO |
| | WALL CONNECTION AND WALL VERTICAL RE-INFORCING. SPECIFY |
| | GROUT TO BE USED IN WALL CELLS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |