| Plan Review Notes For Permit 21080720 |
| Permit Number |
21080720 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-21 12:45:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301, IT APPEARS THE PROPOSED IMPROVEMENT IS | | | OUTDOORS. HOW WILL THIS RESIST WIND LOADS? | | | | | | 2. FS471, THE TITLE BLOCK OF SAGE ENGINEERING IS ON THE | | | PLANS (GAS PLAN, LAYOUT PHOTO PAGES, CHECK ALL). MR. | | | GAYDOSH'S LICENSE WAS REVOKED IN 2019 PER DBPR WEBSITE. | | | THE TITLE "ENGINEER" CAN ONLY BE USED BY INDIVIDUALS | | | LICENSED BY FBPE. SINCE HE IS NOT SIGNING AND SEALING | | | THIS PLAN, IT IS NOT CLEAR WHY HIS TITLE BLOCK WOULD BE | | | ON THE PLAN. REMOVE OR PROVIDE CLARIFICATION. | | | | | | 3. PAGE 2 OF 4 (SLAB CERTIFICATION) LACKS A TITLE BLOCK | | | AS REQUIRED BY FS481. CHECK ALL PAGES. |
|