| Plan Review Notes For Permit 21080700 |
| Permit Number |
21080700 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-10-07 11:55:18 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FPC 1003.3.8 - THE GREASE INTERCEPTOR MUST | | | CONNECT DIRECTLY TO THE SANITARY. | | | | | | 2. 2020 FPC - 607.1.1 - ALL HOT WATER MUST GO THROUGH A | | | MIXING DEVICE. THE THERMOSTAT FOR THE WATER HEATER | | | SHALL NEVER SERVE AS THE TEMPERATURE LIMITING MEANS FOR | | | THE PURPOSES OF COMPLYING WITH THE REQUIREMENTS FOR | | | ALLOWABLE HOT OR TEMPERED WATER. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|