| 2022-05-25 15:33:14 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21080700 |
| | 5/25/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P101: SHEET A000 CLASSIFIES THE SPACE AS A B |
| | OCCUPANCY HOWEVER THE FIXTURE CALCULATIONS ARE |
| | INDICATING AN M OCCUPANCY. PLEASE CHOOSE ONE OR THE |
| | OTHER- SEC. 107.2.1 WPB. |
| | |
| | 2) P101: THE MOP SINK DRAINAGE SHALL BE DISCHARGED INTO |
| | THE GREASE INTERCEPTOR- SEC. 1003.3.1 FBC P. |
| | |
| | 3) P101: EACH WELL OF THE 3-COMPARTMENT SINK SHALL |
| | DISCHARGE INDIRECTLY INTO A WASTE RECEPTOR- SEC. |
| | 802.1.1 FBC P. |
| | |
| | 4) P101: TEMPERED WATER SHALL BE DELIVERED FROM |
| | LAVATORIES HAVING BOTH HOT AND COLD WATER SUPPLIED TO |
| | THE FIXTURE- SEC. 419.5 FBC P. PLEASE PROVIDE AN ASSE |
| | 1070 MIXING VALVE FOR THE SUPPLY PIPING- SEC. 607.1.2. |
| | |
| | 5) P101: A MEANS OF LIMITING THE HOT WATER DELIVERY |
| | TEMPERATURE TO THE MOP SINK AND HAND SINK SHALL BE |
| | PROVIDED AND CANNOT BE THE THERMOSTAT ON THE WATER |
| | HEATER- SEC. 607.1.1 FBC P. PROVIDE EITHER A MASTER |
| | THERMOSTATIC MIXING VALVE AT THE WATER HEATER OR A |
| | POINT OF USE MIXING VALVE AT THE FIXTURES. |
| | |
| | 6) P101: THE 1/2-INCH HW LAVATORY FIXTURE SUPPLY PIPE |
| | IS EXCEEDING THE MAXIMUM 2 FT. ALLOWABLE LENGTH FROM |
| | THE SOURCE OF THE HW- SEC AND TABLE C404.1 FBC EC. |
| | PROVIDE EITHER A RECIRCULATION PUMP FOR THE SYSTEM OR A |
| | POINT OF USE WATER HEATER AT THE LAVATORY. |
| | |
| | 7) P101: DUE TO A CHANGE IN PROCESS, THE GREASE |
| | INTERCEPTOR PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO |
| | ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |