| 2021-09-09 10:18:24 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21080700 | | | 9/8/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SECTIONS 107.21 & 107.3.5.1.3 WPB & FBC P: PROVIDE | | | PLUMBING PLANS AND SPECIFICATIONS INCLUDING- | | | | | | A) PLUMBING FIXTURE CALCULATIONS FOR THE CHANGE OF USE- | | | TABLE 403.1 FBC P. | | | B) PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS. | | | C) PLUMBING EQUIPMENT SCHEDULE. | | | D) FOOD EQUIPMENT PLAN AND SCHEDULE | | | E) GREASE WASTE DISPOSAL AND INTERCEPTOR PLANS AND | | | SPECIFICATIONS. PLEASE NOTE A SEPARATE PERMIT IS | | | REQUIRED FOR NEW GREASE INTERCEPTOR INSTALLATIONS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|