| 2021-08-17 17:45:17 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/RPX306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: PROPOSED SOW IS THE INSTALLATION OF ENGINEERED | | | HARDWOOD FLOORING OVER APPROVED UNDERLAYMENT. | | | | | | 1. ASTM E-492 TEST SPECIMEN UTILIZED AN 8 INCH SLAB | | | WITH SUSPENDED GYPSUM BOARD CEILING AND 3 1/2 INCH | | | INSULATION OVERLAID WITH PORCELAIN TILE AND PRO=FLEX | | | MSC 90 UNDERLAYMENT. | | | | | | 2. ASTEM E-90 UTILIZED AN 8 INCH SLAB FLOOR CEILING | | | ASSEMBLY OVERLAID WITH QUARRY TILE USING PROFLEX MSC 90 | | | UNDERLAYMENT. | | | | | | 3. ASTM E-84 UTILIZED PRO-FLEX SUPER SIM-90 | | | UNDERLAYMENT. | | | | | | PROVIDE ASTM TEST REPORTS FOR THE PROPOSED ENGINEERED | | | HARDWOOD FLOORING. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|