| Notes |
| Date |
Text |
| 2021-09-25 09:37:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1207, THE FLOORING UNDERLAYMENT PROPOSED WAS | | | TESTED ON AN 8" SLAB. THE RECORDS FOR THIS BUILDING | | | SHOW A 7" POST TENSION SLAB. EITHER PROVIDE TEST | | | REPORTS WITH A 7" OR THINNER SLAB, OR PROPOSE A | | | DIFFERENT UNDERLAYMENT. | | | | | | 2. THE FLAME SPREAD TEST WAS DONE WITH TILE (RESULT | | | WILL TYPICALLY BE 0), BUT TILE IS NOT THE FLOORING | | | PROPOSED, LVT IS PROPOSED. EITHER PROVIDE THE FLAME | | | SPREAD TEST OR CONSIDER PROFLEX'S PRODUCT FOR LVT | | | (PROFLEX LV200). | | | | | | 3. FBC 107 REQUIRES THAT THE PERSON TAKING | | | RESPONSIBLITY FOR THE DESIGN INCLUDE THEIR PRINTED NAME | | | AND SIGNATURE ON EACH PAGE. ONLY FOR PAGES THAT CHANGE | | | AND FOR FUTURE PROJECTS, HAVE THE DESIGNER INCLUDE THIS | | | INFORMATION. | | | | | | | | | | | | |
|