| 2021-09-09 08:20:39 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21080643 |
| | 9/9/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P0.1 & P1.1. PROVIDE A PLUMBING FIXTURE |
| | SCHEDULE THAT INCLUDES THE MOP SINK, BREAKROOM SINK, |
| | FAUCETS, WASHING MACHINE- SECTIONS 406, 418, & 424 FBC |
| | P. |
| | |
| | 2) P0.1 & P1.1: SHOW THE LOCATIONS OF REQUIRED WATER |
| | HAMMER ARRESTORS AND BACKFLOW PREVENTERS ON SUPPLY |
| | LINES TO THE REFRIGERATOR ICE MAKERS IN THE BREAKROOM, |
| | AND THE ICE MACHINE IN THE EXISTING WAREHOUSE- SECTIONS |
| | 604.9 & 608.3 FBC P. CLARIFY IF WALL BOXES WILL BE |
| | INSTALLED AT THE REFRIGERATOR LOCATIONS- SECTION |
| | 107.2.1 WPB. |
| | |
| | 3) ) P0.1 & P1.1: SHOW THE LOCATIONS OF REQUIRED WATER |
| | HAMMER ARRESTORS AND BACKFLOW PREVENTERS ON SUPPLY |
| | LINES TO THE WASHING MACHINE IN THE EXISTING WAREHOUSE- |
| | SECTIONS 604.9 FBC P. CLARIFY IF A WALL BOXES WILL BE |
| | INSTALLED AT THE MACHINE LOCATION- SECTION 107.2.1 WPB. |
| | |
| | 4) P0.1 & P1.1: PROVIDE AN INTERCEPTOR FOR THE WASHING |
| | MACHINE DISCHARGE- SECTION 1003.6 FBC P. PLEASE NOTE AN |
| | INTERCEPTOR IS NOT AN INTEGRAL FILTER. |
| | |
| | 5) P0.1 & P1.1: PLEASE REVIEW AND SUBMIT THE |
| | MANUFACTURER'S SPECIFICATIONS FOR THE ICE MACHINE TO |
| | VERIFY A FLOOR DRAIN IS NOT REQUIRED TO CONVEY ICE |
| | DRAINAGE OR CONDENSATION FROM THE MACHINE- SECTION |
| | 314.2.1 FBC P. |
| | |
| | 6) P1.1: SHOW A 2-INCH STANDPIPE CONNECTIONG TO A |
| | 3-INCH STACK AT THE WASHING MACHINE- SECTION 406.1 FBC |
| | P. |
| | |
| | 7) A3.0: PAINTED GWB IS NOT APPROVED FOR INSTALLATION |
| | ON THE WALLS SURROUNDING THE MOP SINK. A SMOOTH, HARD, |
| | NONABSORBENT SURFACE MATERIAL IS REQUIRED TO BE |
| | INSTALLED TO A HEIGHT OF NOT LESS THAN 4 FT. ABOVE THE |
| | FLOOR- SECTION 1210.2.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |