| Plan Review Notes For Permit 21080643 |
| Permit Number |
21080643 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-27 10:08:36 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21080643 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE | | | OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR NEW RTU-34. FBC EC C403.2.1 | | | | | | 3) SHEET M1.1: THE MEETING ROOM APPEARS TO HAVE RATED | | | WALLS. RTU-24 APPEARS TO BE SPLIT BY THE NEW RATED | | | WALL. PLEASE SHOW A DETAIL OF HOW THIS INSTALLATION IS | | | GOING TO WORK. FBC M 607 | | | | | | 4) THERE ARE SEVERAL DUCTS PENETRATING THE NEW RATED | | | WALLS OF THE MEETING ROOM. PLEASE SHOW HOW THE | | | PENETRATION OF THE DUCT AT THESE WALLS WILL BE | | | PROTECTED. FBC M 607 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|