| 2021-09-03 18:53:21 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21080635 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- SHUTTER SPAN FOR OPENING #1 EXCEEDS THE MAXIMUM SPAN |
| | ALLOWED BY TABLE 3 ON PAGE 1 OF 14 OF SHUTTERS PRODUCT |
| | APPROVAL SUBMITTED. REVISE AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- SPACING OF ANCHOR AT THE BOTTOM OF OPENING #2 NEEDS |
| | TO BE REVISED. SEE PAGE 11 OF 14 OF SHUTTERS PRODUCT |
| | APPROVAL SUBMITTED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- CLEARLY SPECIFY HOW THE EMERGENCY EGRESS IS ACHIEVED |
| | IF ALL OPENINGS WILL HAVE SHUTTERS? SEC. R310.4 |
| | FBC-RESIDENTIAL. |
| | |
| | |
| | 4- BASED ON THE OPENING HEIGHT AND THE EDGE DISTANCE |
| | SPECIFIED ON THE INSTALLATION SCHEDULE, IT LOOKS LIKE |
| | THE SPECIFIED SHUTTER SPAN IS INCORRECT. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | NOTE: |
| | CLEARLY SPECIFY IF THE EDGE DISTANCE SHOWN INCLUDES THE |
| | STUCCO THICKNESS OR NOT. THIS IS IMPORTANT BECAUSE IN |
| | THE FIELD THE ACTUAL EDGE DISTANCE NEED TO BE LARGER |
| | THAN THE ONE SHOWN ON THE SCHEDULE (TYPICALLY 1/2 MORE |
| | TO INCLUDE THE STUCCO THICKNESS). |
| | |
| | THE EDGE DISTANCE IS THE ONE THAT WILL BE VERIFIED IN |
| | THE FIELD. IF THE EDGE DISTANCE IS LESS THAN THE |
| | SPECIFIED ONE, THEN A REVISION WILL BE REQUIRED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |