Plan Review Notes
Plan Review Notes For Permit 21080634
Permit Number 21080634
Review Stop P
Sequence Number 2
Notes
Date Text
2022-01-12 08:17:2601/12/22 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THERE IS A SHOWER OUTSIDE WITH A DRAIN CONNECTED TO
 THE SANITARY. ONLY APPURTENANCES AND APPLIANCES USED TO
 RECEIVE OR DISCHARGE LIQUID WASTES OR SEWAGE SHALL BE
 DIRECTLY CONNECTED TO THE SANITARY PER THE 2020 FBC
 SEC. R 2601.2 CONNECTIONS TO THE DRAINAGE SYSTEM, AND
 YOU MAY DISCHARGE TO A DRY WELL OR GRASSY LOCATION.
  
 THE ARCHITECT WAS CONTACTED AND THEY SAID THE NEW
 DRAWING WERE NEVER UPLOADED AND I INSTRUCTED THEM TO
 SEND TO ME SO I CAN UPLOAD AND PASS PLUMBING, CALLED
 TWICE AFTER THE FIRST CONVERSATION AND NO AVAIL.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  