| 2022-01-12 08:17:26 | 01/12/22 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THERE IS A SHOWER OUTSIDE WITH A DRAIN CONNECTED TO |
| | THE SANITARY. ONLY APPURTENANCES AND APPLIANCES USED TO |
| | RECEIVE OR DISCHARGE LIQUID WASTES OR SEWAGE SHALL BE |
| | DIRECTLY CONNECTED TO THE SANITARY PER THE 2020 FBC |
| | SEC. R 2601.2 CONNECTIONS TO THE DRAINAGE SYSTEM, AND |
| | YOU MAY DISCHARGE TO A DRY WELL OR GRASSY LOCATION. |
| | |
| | THE ARCHITECT WAS CONTACTED AND THEY SAID THE NEW |
| | DRAWING WERE NEVER UPLOADED AND I INSTRUCTED THEM TO |
| | SEND TO ME SO I CAN UPLOAD AND PASS PLUMBING, CALLED |
| | TWICE AFTER THE FIRST CONVERSATION AND NO AVAIL. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, DESCRIBING THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |