| 2021-10-18 14:45:28 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 9.) FBC B 904.1 - FBC A 904.4.2, PROVIDE ON PLANS THE |
| | REQUIRED ACCESSIBLE DETAILS FOR CHECK OUT COUNTERS PER |
| | THE FBC ACCESSIBILITY CODE. THE CONTRACTOR WILL BE |
| | REQUIRED TO COMPLY WITH THOSE REQUIREMENTS. |
| | |
| | |
| | PROVISOS: |
| | |
| | 2.) FBC M 306.5, THE ROOF DECK MUST NOT REQUIRE |
| | CLIMBING OVER OBSTRUCTIONS GREATER THAN 30" IN HEIGHT |
| | AND PORTABLE LADDERS SHALL NOT BE REQUIRED BETWEEN THE |
| | ROOF ACCESS HATCH AND AND ROOF/ROOF TOP UNITS. |
| | |
| | 5B.) AWS D1.1 CLAUSE 5.2 & 6.7: AT TIME OF INSPECTION |
| | PLEASE PROVIDE A WELD PROCEDURE SPECIFICATION; THE |
| | W.P.S. SPECIFIES THE REQUIRED ESSENTIAL VARIABLES |
| | INCLUDING: BASE MATERIALS, JOINTS, PROCESS, AND FILLER |
| | METALS TO BE USED. |
| | AWS D1.1 CLAUSE 6.16: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| | NOTE: A THIRD PARTY WILL BE REQUIRED TO CERTIFY |
| | WELD/BOLT CONNECTIONS. |
| | |
| | 6.) FBC B 107.2, AT TIME OF INSPECTION PROVIDE |
| | MANUFACTURER'S ROOF TOP EQUIPMENT TO CURBS AND CURBS TO |
| | ROOF FRAMING CONNECTION (ENGINEER SIGNED/SEALED) |
| | DETAILS. THESE DETAILS MUST BE IN ACCORDANCE WITH THE |
| | WIND LOAD REQUIREMENTS SHOWN ON SHEET S 001. |
| | |
| | |