Plan Review Notes
Plan Review Notes For Permit 21080615
Permit Number 21080615
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-24 12:26:0309/24/21 1ST POOL REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET C1, ON #1, THERE IS A DETAIL FOR TOILET AND
 ACCESSORY DETAIL BUT NO DETAIL THAT PROVIDES THE 2020
 FBC ACCESSIBILITY CODE. WOULD YOU PLEASE PROVIDE A PAGE
 AND SHOW THE FLOWING PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS;
  
 A. PLEASE SHOW CLEAR FLOOR SPACE AND GIVE DIMENSIONS
 FOR FIXTURE CLEARANCES PER FLORIDA BUILDING CODE FOR
 THE FLORIDA ACCESSIBILITY CODE, ONE OF THE ELECTRIC
 WATER COOLERS, EYEWASH, SINK IN THE LOUNGE, WATER
 CLOSET AND LAV IN THE STALLS, ONE LAV OUTSIDE THE
 STALL, AND URINAL PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE TOILET SEATS NEED TO BE 17 INCHES TO 19 INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020
 FBC ACC SEC. 604.4 SEATS.
  
 C. WOULD YOU PLEASE SHOW THE HARDWARE, WHICH SHALL BE
 34 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND, AND HARDWARE SHALL BE EXPOSED
 AND USABLE FROM BOTH SIDES PER THE 2020 FBC ACC. SEC.
 404.2.7.
  
 D. WOULD YOU SHOW THE GRAB BARS PER THE 2020 FBC ACC
 SEC. 604.5.1 SIDE WALL AND 604.5.2 REAR WALL. THE GRAB
 BARS SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE PER THE 2020 FBC ACC SEC. 609.4.
  
 E. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION PER THE 2020 FBC ACC SEC. 609.4.
  
 F. SHOW THE TOILET IS 16 INCHES TO 18 INCHES TO THE
 CENTER PER THE 2020 FBC ACC SEC. 604.2 LOCATION. THE
 CLEAR FLOOR SPACE SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDEWALL, AND 56 INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL PER THE 2020
 FBC ACC. SEC. 604.3.1.
  
 G. THE TOILET PAPER DISPENSERS SHALL BE 7 INCHES
 MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER PER
 THE 2020 FBC ACC SEC. 604.7.
  
 H. HANDICAP CAP WATER CLOSET FLUSH CONTROL SHALL BE
 HAND OPERATED OR AUTOMATIC AND SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND ON THE OPEN SIDE PER
 THE 2020 FBC ACC SEC. 604.9.5.
  
 J. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 K. THE URINALS SHALL BE 17 INCHES SHALL BE A MAXIMUM
 AND 13 1/2 INCHES PER THE 2020 FBC ACC. SEC. 605.2.
  
 L. THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE 40
 INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC.
 603.3.
  
 M. SHOW THE HEIGHT FOR ALL PARTITIONS IN BETWEEN THE
 2020 FBC SEC. P 405.3.5. THE WALLS OR PARTITIONS SHALL
 BEGIN AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND
 EXTEND NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR
 SURFACE.
  
 N. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 2. ON SHEET P001;
  
 A. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 B. FOR THE EYEWASH STATION, THE TEMPERATURE OF THE
 WATER SUPPLY SHALL ONLY BE CONTROLLED BY A
 TEMPERATURE-ACTUATED MIXING VALVE COMPLYING WITH ASSE
 1071 PER THE 2020 FBC P 411.3 WATER SUPPLY.
  
 C. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2020 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
  
 D. IF AN ICEMAKER OR COFFEE MAKER IS PROVIDED, THEY
 SHALL BE EQUIPPED WITH AN IN-LINE VACUUM BREAKER THAT
 COMPLIES WITH ASSE 1024 PER THE 2020 FBC SEC.
 608.13.10.
  
 E. ON THE EWH DETAIL, PLEASE SHOW THE THERMAL EXPANSION
 DEVICE PER THE 2020 FBC SEC P 607.3.
  
  
 3. ON SHEET P101;
  
 A. WOULD YOU PLEASE SHOW THE MAIN SHUT-OFF VALVE FOR
 THE STRUCTURE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 IT IS NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT
 IN THE FLORIDA ENERGY CODE SEC. C404.6.1.
  
 C. THERE IS A TABLE THAT LIMITS THE BETWEEN THE SOURCE
 AND THE OUTLET; PLEASE REFER TO TABLE 405.5.1 FOR THE
 MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY.
  
 D. THE WC-2 IN WOMEN'S AND MEN'S ROOMS NEEDS TO BE
 LABELED AS A LAV. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. IF POSSIBLE, SHOW RECIRCULATING PUMP AND SHUT-OFF
 VALVES IN THE WATER HEATER LOCATION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET P102;
  
 A. ON THE ISOMETRIC ON THE MEN'S RESTROOM, IT SHOWS A
 WC-2, THEN IT SHOULD BE A LAV THEN URINAL, AND ON THE
 WOMEN'S WC-2 NEEDS TO BE A LAV. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE LABEL ALL LAVS ON THE ISOMETRIC PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE SHOW THE TRAP PRIMERS ON THE FLOOR
 DRAINS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. WOULD YOU, PLEASE SIZE THE EYEWASH ON THE ISOMETRIC
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. WOULD YOU, PLEASE SHOW THE CLEAN-OUT OUTSIDE THE
 BUILDING DRAIN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  