2022-01-12 16:07:54THE FLORIDA BUILDING CODE MECHANICAL SECTION 403.3.1.1
 AND TABLE 403.3.1.1 DICTATES THAT WE USE THE
 VENTILATION TABLE TO CALCULATE THE OUTDOOR AIR REQUIRED
 FOR THE USE OF SPACE IN ALL BUILDINGS. THE TABLE HAS A
 PARTICULAR MINIMUM OCCUPANT DENSITY THAT WE USE TO
 CALCULATE THE OCCUPANTS FOR EACH SPACE. WE DO NOT USE
 THE ARCHITECTURAL OCCUPANT COUNT TO SIZE THE MECHANICAL
 SYSTEMS UNLESS THE ARCHITECT?S OCCUPANT COUNT IS HIGHER
 THAN THE MINIMUM REQUIRED BY TABLE 403.3.1.1 IN THE
 MECHANICAL CODE BOOK. UPON REVIEWING THE OUTDOOR AIR
 CALCULATIONS FOR THIS PROJECT I SEE THAT THE CONFERENCE
 ROOMS AND THE LOBBY IN THE 1900 AND IN 2000 HAVE NOT
 BEEN SIZED USING THE TABLE 403.3.1.1 FOR THE OUTDOOR
 AIR CALCULATIONS. THE OUTDOOR AIR NUMBERS ARE LOW
 COMPARED TO WHAT WOULD BE REQUIRED. ONE EXAMPLE IS
 ROOMS ?1901/1931/1934 TRAINING? IT IS LISTED AS
 CONFERENCE/MEETING WITH A TOTAL SQUARE FOOTAGE AS 2,351
 WITH TOTAL OUTDOOR AIR REQUIRED AS 401.06 CFM?S. THE
 CALCULATION IS ? 2351/1000 = 2.351; 2.351 X 50 = 117.55
 OR 118 OCCUPANTS; 118 X 5CFM = 590CFM; 2351 X .06 =
 141.06CFM; 590 + 141.06 = 731.06 OR 731 CFM?S OF
 OUTDOOR AIR REQUIRED FOR THIS SPACE. PLEASE CORRECT THE
 AREAS THAT WERE NOT CALCULATED USING THE TABLE
 403.3.1.1 AND RESUBMIT THE OUTDOOR AIR CALCULATIONS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER