2021-12-02 14:17:013RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21080610
 12/2/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEWS ARE LISTED BELOW WITH ADDITONAL
 NOTES IN CAP LETTERS FOR FURTHER CLARIFICATIONS. PLEASE
 NOTE THAT THE REQUESTED RESPONSE NARRATIVE TO THE 2ND
 REVIEW COMMENTS WAS NOT PROVIDED, AND THE ARCHITECTURAL
 PLAN SHEETS SHOWING ACCESSIBILITY COMPLIANCES WERE NOT
 CORRECTED.
  
 1) FAILED. SHEET A101: SHOW THE CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS FOR THE ACCESSIBLE SINKS IN
 ROOMS 1905, 1929, & 1935- SECTION 606.2 FBC ACC. NOT
 PROVIDED.
  
 2) FAILED. A108, A401: THE REQUIRED CLEAR FLOOR SPACE
 FOR THE WATER CLOSET IN PRIVATE OFFICE BATHROOM 2025
 HAS NOT BEEN PROVIDED, AND WILL OVERLAP THE LAVATORY-
 SECTIONS 604.3.1 & 604.3.2 FBC ACC. NOT PROVIDED.
  
 4) FAILED ITEMS A, B, D, E, F, G, H, I, J. A401 & A402:
 FBC ACCESSIBILITY CORRECTIONS AND MISSING DETAILS FOR
 MEN'S AND WOMEN'S BATHROOMS.
 A) TURNING SPACE DIAGRAMS AND DIMENSIONS IN THE
 WHEELCHAIR ACCESSIBLE COMPARTMENTS- 304.3.
 B) LENGTH AND SPACING MEASUREMENTS FOR THE REAR AND
 SIDE WALL WATER CLOSET GRAB BARS IN THE WHEELCHAIR
 ACCESSIBLE COMPARTMENTS AND THE AMBULATORY
 COMPARTMENTS- 604.5
 D) REMOVE VERTICAL GRAB BARS. THEY ARE NOT REQUIRED PER
 FBC ACC AND ARE IN CONFLICT WITH 609.4 WHICH REQUIRES
 GRAB BARS TO BE INSTALLED IN A HORIZONTAL POSITION.
 E) INDICATE MIRROR MEASUREMENTS TO THE REFLECTIVE
 SURFACES AND NOT THE BOTTOM OF THE MIRRORS- 603.3.
 F) HEIGHTS OF THE LAVATORIES IN THE ACCESSIBLE
 COMPARTMENTS- 606.3.
 G) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE
 LAVATORIES- 306.2, 306.3, & 606.2.
 H) RELOCATE WATER CLOSET FLUSH CONTROLS TO THE OPEN
 SIDES OF THE FIXTURES- 604.6.
 I) URINAL RIM HEIGHT FOR THE FLOOR- 605.2.
 J) HEIGHT OF THE PAPER TOWEL DISPENSER- 308.
  
 3) FAILED ITEMS A, B, C, D. A401 & A403: FBC ACC
 CORRECTIONS AND MISSING DETAILS FOR PRIVATE OFFICE
 BATHROOM 2025.
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2. (NOTE- ITEM 1 EXEMPTS THE KNEE
 AND TOE CLEARANCES.)
 C) TURNING SPACE DIAGRAM AND DIAMETER- 304.3.
 D) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- 603.3.
 E) WATER CLOSET GRAB BAR REINFORCEMENT LOCATIONS BASED
 ON SECTIONS 604.5 & 609.4.
  
 4) FAILED ITEM A. A401 & A403: FBC ACC CORRECTIONS AND
 MISSING DETAILS FOR PRIVATE OFFICE BATHROOM 2050.
 A) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3.
  
 5) FAILED ITEMS A, B, C, E, F. A401 & A403: FBC ACC
 CORRECTIONS AND MISSING DETAILS FOR UNISEX BATHROOMS
 1928 & 2040.
 A) THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACES FOR THE LAVATORIES- 603.2.3.
 B) REMOVE VERTICAL GRAB BARS. THEY ARE NOT REQUIRED PER
 FBC ACC AND ARE IN CONFLICT WITH 609.4 WHICH REQUIRES
 GRAB BARS TO BE INSTALLED IN A HORIZONTAL POSITION.
 C) INDICATE MIRROR MEASUREMENTS TO THE REFLECTIVE
 SURFACES AND NOT THE BOTTOM OF THE MIRRORS- 603.3.
 E) HEIGHTS OF THE ACCESSIBLE LAVATORIES- 606.3.
 F) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE
 LAVATORIES- 306.2, 306.3, & 606.2.
  
 6) FAILED ITEMS A, B. A405: FBC ACC CORRECTIONS AND
 MISSING DETAILS FOR ROOMS 1905, 1917, 1929, & 1935.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR SINKS,
 DISHWASHERS, REFRIGERATORS- 686.2 & 804.6.
 B) CLEAR FLOOR SPACES, REACH HEIGHTS, AND OPERABLE PART
 COMPLIANCE FOR APPLIANCES INCLUDING THE COFFEE
 DISPENSER AND MICROWAVES- 309 & 804.6.2.
  
 7) FAILED. A401: REFER TO SECTIONS 306, 307, AND 602
 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES. INDICATE HOW COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS IS BEING MET.
  
 8) FAILED. A403: PREVIOUS REVIEW REQUEST TO PROVIDE
 NON-ABSORBENT WALL FINISH MATERIALS FOR THE MOP SINK
 SURROUNDS WAS NOT PROVIDED- SECTION 1210.2.2 FBC B.
  
 9) FAILED. P202 & P203: PLEASE ADD THE NOTES FOR THE
 BACKFLOW PREVENTER AND WATER HAMMER ARRESTOR FOR THE
 SUPPLY LINE TO THE COFFEE MAKER- SEE NOTES ON P202.
 PLEASE SEE TABLE 608.3 & SECTION 608.17.1.2 FBC P- THE
 ASSE 1024 STANDARD IS APPLICABLE TO
 DUAL-CHECK-VALVE-TYPE BACKFLOW PREVENTERS NOT INLINE
 VACUUM BREAKERS.
  
 10) FAILED. P402: HWR & HW LINE SYMBOLS ARE NOT SHOWN
 CORRECTLY ON THE 19TH FLOOR DOMESTIC WATER PLAN-
 SECTION 107.2.1 WPB. SOLID LINES INSTEAD OF BROKEN
 LINES ARE MISREPRESENTING HWR & HW LINES.
  
 12) FAILED. P601 DETAIL 1: THE HWR LINE SHALL BE ROUTED
 TO THE COLD WATER INLET PIPE OF THE WATER HEATER AND
 THE COLD WATER INLET PIPE CONNECTION TO THE MASTER
 THERMOSTATIC MIXING VALVE- SECTION 607.2.2 FBC P. NO
 CHANGES WERE MADE TO THE DETAIL TO SHOW COMPLIANCE.
  
 13) FAILED. P503 & P601: PLEASE INDICATE HOW TEMPERED
 WATER WILL BE DELIVERED FROM THE LAVATORY FAUCETS-
 SECTION 419.5 FBC P. A MASTER MIXING VALVE PROVIDED.
 PLEASE INDICATE THE TEMPERATUURE OF THE WATER BEING
 SUPPLIED TO THE PLUMBING FIXTURES. PLEASE NOTE THE
 REQUIRED TEMPERED WATER AT THE LAVATORIES SHALL BE AT A
 TEMPERATURE RANGE BETWEEN 85 AND 110 DEGREES. HOT WATER
 HAS A TEMPERATURE OF 110 DEGREES OR GREATER- SECTION
 202.
  
 14) FAILED. P602: THE REQUESTED UL FIRESTOPPING
 ASSEMBLIES FOR INSULATED AND NON-INSULATED PIPE
 PENETRATIONS WAS NOT PROVIDED. THE NARRATIVE REFERENCES
 SHEETS A603 & A604 HOWEVER THE DETAILS ARE NOT SHOWN ON
 THOSE SHEETS- SECTION 315.1 FBC P AND SECTION 714.4.1.2
 FBC B. NOT PROVIDED.
  
 15) FAILED. P701: PLEASE PROVIDE SCHEDULES FOR THE
 WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW
 PREVENTERS, AND TRAP PRIMERS- SECTIONS 604.9, 607.2.1,
 608.3, AND 1002.4.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  