Plan Review Notes
Plan Review Notes For Permit 21080610
Permit Number 21080610
Review Stop B
Sequence Number 3
Notes
Date Text
2021-11-23 13:55:57OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) REST ROOMS (1927) AND (2040) FBC 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS: (2.) WHERE THE TOILET ROOM OR BATHING ROOM
 IS FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE. (PLEASE SHOW THE CLEAR FLOOR SPACE)
  
 2) PLEASE SHOW THE TYPE OF FIRE PROTECTION AND THE
 HOURLY FIRE RATING REQUIRED FOR THE STRUCTURAL STEEL
 BEAMS FBC TABLE 601
  
 3) BUILDING CONSTRUCTION TYPE SHOULD BE SHOWN PER FBC
 602.1