Plan Review Notes
Plan Review Notes For Permit 21080610
Permit Number 21080610
Review Stop P
Sequence Number 2
Notes
Date Text
2021-11-10 11:39:592ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21080610
 11/9/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE
 FOLLOW-UP TO 1ST REVIEW COMMENTS AND REVIEW OF THE
 REVISED PLANS AND RESPONSE NARRATIVE.
  
 1) SHEET A101: SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE ACCESSIBLE SINKS IN ROOMS 1905,
 1929, & 1935- SECTION 606.2 FBC ACC.
  
 2) A108, A401: THE REQUIRED CLEAR FLOOR SPACE FOR THE
 WATER CLOSET IN PRIVATE OFFICE BATHROOM 2025 HAS NOT
 BEEN PROVIDED, AND WILL OVERLAP THE LAVATORY- SECTIONS
 604.3.1 & 604.3.2 FBC ACC.
  
 4) A401 & A402: FBC ACCESSIBILITY CORRECTIONS AND
 MISSING DETAILS FOR MEN'S AND WOMEN'S BATHROOMS.
 A) TURNING SPACE DIAGRAMS AND DIMENSIONS IN THE
 WHEELCHAIR ACCESSIBLE COMPARTMENTS- 304.3.
 B) LENGTH AND SPACING MEASUREMENTS FOR THE REAR AND
 SIDE WALL WATER CLOSET GRAB BARS IN THE WHEELCHAIR
 ACCESSIBLE COMPARTMENTS AND THE AMBULATORY
 COMPARTMENTS- 604.5
 C) SHOW GRAB BAR HEIGHTS TO THE TOPS OF THE GRIPPING
 SURFACES- 609.4.
 D) REMOVE VERTICAL GRAB BARS. THEY ARE NOT REQUIRED PER
 FBC ACC AND ARE IN CONFLICT WITH 609.4 WHICH REQUIRES
 GRAB BARS TO BE INSTALLED IN A HORIZONTAL POSITION.
 E) INDICATE MIRROR MEASUREMENTS TO THE REFLECTIVE
 SURFACES AND NOT THE BOTTOM OF THE MIRRORS- 603.3.
 F) HEIGHTS OF THE LAVATORIES IN THE ACCESSIBLE
 COMPARTMENTS- 606.3.
 G) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE
 LAVATORIES- 306.2, 306.3, & 606.2.
 H) RELOCATE WATER CLOSET FLUSH CONTROLS TO THE OPEN
 SIDES OF THE FIXTURES- 604.6.
 I) URINAL RIM HEIGHT FOR THE FLOOR- 605.2.
 J) HEIGHT OF THE PAPER TOWEL DISPENSER- 308.
  
 3) A401 & A403: FBC ACC CORRECTIONS AND MISSING DETAILS
 FOR PRIVATE OFFICE BATHROOM 2025.
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2. (NOTE- ITEM 1 EXEMPTS THE KNEE
 AND TOE CLEARANCES.)
 C) TURNING SPACE DIAGRAM AND DIAMETER- 304.3.
 D) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- 603.3
 E) WATER CLOSET GRAB BAR REINFORCEMENT LOCATIONS BASED
 ON SECTIONS 604.5 & 609.4.
  
 4) A401 & A403: FBC ACC CORRECTIONS AND MISSING DETAILS
 FOR PRIVATE OFFICE BATHROOM 2050.
 A) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 B) WATER CLOSET GRAB BAR REINFORCEMENT LOCATIONS BASED
 ON SECTIONS 604.5 & 609.4.
  
 5) A401 & A403: FBC ACC CORRECTIONS AND MISSING DETAILS
 FOR UNISEX BATHROOMS 1928 & 2040.
 A) THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACES FOR THE LAVATORIES- 603.2.3.
 B) REMOVE VERTICAL GRAB BARS. THEY ARE NOT REQUIRED PER
 FBC ACC AND ARE IN CONFLICT WITH 609.4 WHICH REQUIRES
 GRAB BARS TO BE INSTALLED IN A HORIZONTAL POSITION.
 C) INDICATE MIRROR MEASUREMENTS TO THE REFLECTIVE
 SURFACES AND NOT THE BOTTOM OF THE MIRRORS- 603.3.
 E) HEIGHTS OF THE ACCESSIBLE LAVATORIES- 606.3.
 F) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE
 LAVATORIES- 306.2, 306.3, & 606.2.
  
 6) A405: FBC ACC CORRECTIONS AND MISSING DETAILS FOR
 ROOMS 1905, 1917, 1929, & 1935.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR SINKS,
 DISHWASHERS, REFRIGERATORS- 686.2 & 804.6.
 B) CLEAR FLOOR SPACES, REACH HEIGHTS, AND OPERABLE PART
 COMPLIANCE FOR APPLIANCES INCLUDING THE COFFEE
 DISPENSER AND MICROWAVES- 309 & 804.6.2.
  
 7) A401: REFER TO SECTIONS 306, 307, AND 602 FBC ACC
 AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. INDICATE HOW COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS IS BEING MET.
  
 8) A403: PREVIOUS REVIEW REQUEST TO PROVIDE
 NON-ABSORBENT WALL FINISH MATERIALS FOR THE MOP SINK
 SURROUNDS WAS NOT PROVIDED- SECTION 1210.2.2 FBC B.
  
 9) P203: PLEASE ADD THE NOTES FOR THE BACKFLOW
 PREVENTER AND WATER HAMMER ARRESTOR FOR THE SUPPLY LINE
 TO THE COFFEE MAKER- SEE NOTES ON P202.
  
 10) P402: HWR & HW LINE SYMBOLS ARE NOT SHOWN CORRECTLY
 ON THE 19TH FLOOR DOMESTIC WATER PLAN- SECTION 107.2.1
 WPB.
  
 11) P502: LABEL THE SIZES OF THE 20TH FLOOR P3 DRAINS
 AND DRAIN STACK SIZES- SECTION 710.1 FBC P.
  
 12) P601 DETAIL 1: THE HWR LINE SHALL BE ROUTED TO THE
 COLD WATER INLET PIPE OF THE WATER HEATER AND THE COLD
 WATER INLET PIPE CONNECTION TO THE MASTER THERMOSTATIC
 MIXING VALVE- SECTION 607.2.2 FBC P.
  
 13) P503 & P601: PLEASE INDICATE HOW TEMPERED WATER
 WILL BE DELIVERED FROM THE LAVATORY FAUCETS- SECTION
 419.5 FBC P.
  
 14) P602: THE REQUESTED UL FIRESTOPPING ASSEMBLIES FOR
 INSULATED AND NON-INSULATED PIPE PENETRATIONS WAS NOT
 PROVIDED. THE NARRATIVE REFERENCES SHEETS A603 & A604
 HOWEVER THE DETAILS ARE NOT SHOWN ON THOSE SHEETS-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B.
  
 15) P701: PLEASE PROVIDE SCHEDULES FOR THE WATER HAMMER
 ARRESTORS, MIXING VALVE, THERMAL EXPANSION TANK,
 BACKFLOW PREVENTERS, AND TRAP PRIMERS- SECTIONS 604.9,
 607.2.1, 607.3, 608.3, AND 1002.4.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  