Plan Review Notes
Plan Review Notes For Permit 21080610
Permit Number 21080610
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-02 13:25:5609/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET G002 AND G003, THE UNDER APPLICABLE CODES
 REFER TO THE 2018 AMENDMENT WE USE THE AMENDMENTS TO
 THE FLORIDA BUILDING CODE, 6TH EDITION (2017), CHAPTER
 1, ADMINISTRATION. WE CAN PROVIDE A COPY IF YOU WOULD
 NEED ONE. WOULD YOU PLEASE REMOVE THE PALM BEACH COUNTY
 LOCAL AMENDMENTS EFFECTIVE DECEMBER 31, 2020, IS NOT A
 SUPPORTED REFERENCE? IT DOES NOT APPLY TO THESE PLANS
 PER THE WPB AMENDMENTS TO FBC 102.3 APPLICATION OF
 REFERENCES?
  
 2. ON SHEET A101;
 A. THERE ARE TWO BREAK ROOMS IN 1917, 1935, AND A
 COFFEE IN 1904 AND 1929 WITH SINKS. WOULD YOU PLEASE
 PROVIDE A DETAIL SHOWING THE CLEAR FLOOR SPACE FOR THE
 SINK WHERE APPLICABLE PER THE 2020 FBC SEC? ACC 305.3.
  
 B. IN WOMEN'S AND MEN'S RESTROOMS, THE ACCESSIBLE
 TOILET IN NEW CONSTRUCTION, THE WHEELCHAIR-ACCESSIBLE
 TOILET COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY
 WITHIN IT PER THE 2020 FBC ACC SEC. 604.8.1.6 LAVATORY.
  
 3. ON SHEET A 108, THERE ARE TWO OFFICES WITH RESTROOMS
 TO PRIVATE OFFICES. WOULD YOU PLEASE PROVIDE THE
 ACCESSIBILITY TO COMPLY WITH 2020 FBC ACC SECS. 603 AND
 213.2.
  
 4. ON SHEET A 401;
  
 A. WOULD YOU PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS AND A SCHEDULE SHOWING THE REQUIRED AND
 PROVIDED FIXTURES IN COMPLIANCE WITH THE 2020 FBC TABLE
 403.3 FBC P.
  
 B. THE DETAILS 1A AND 1C, WOULD YOU PLEASE PROVIDE THE
 CLEAR FLOOR SPACE FOR THE LAV AND THE TOILET WITH THE
 DIMENSIONS THE APPLIES PER THE 2020 FBC ACC SEC. 606.2.
 2 CLEAR FLOOR SPACE.
  
 C. ON DETAIL 4A, THE UNISEX RESTROOM ON THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET IS OVERLAPPING WITH A LAV.
 NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED
 WITHIN THE REQUIRED WATER CLOSET CLEARANCE PER THE 2020
 FBC AC SEC. 604.3.2 OVERLAP.
  
 D. ON THAT SAME DETAIL, WOULD YOU PLEASE PROVIDE THE
 CLEAR FLOOR SPACE DIMENSIONS FOR THE TRUING RADIUS,
 LAVS, AND WATER CLOSET PER THE 2020 FBC ACC SEC. 606.2.
 2 CLEAR FLOOR SPACE.
  
 E. ON DETAIL 4A WOMEN'S AND MEN'S RESTROOMS, THERE IS
 AN ACCESSIBLE STALL THAT HAS A WATER CLOSET SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT PER THE 2020
 FBC ACC SEC. 604.8.1.6 604.8.1.6 LAVATORY.
  
 F. ON THOSE RESTROOMS, SOME STALLS SEEM TO BE
 AMBULATORY, AND IF SO, THE DOOR WILL REQUIRE TO SWING
 TO THE OUTSIDE PER THE 604.8.2 AMBULATORY ACCESSIBLE
 COMPARTMENTS.
  
 G. ON DETAIL 4A WOMEN'S AND MEN'S REST, WOULD YOU
 PLEASE PROVIDE THE CLEAR FLOOR SPACE DIMENSIONS FOR THE
 TRUING RADIUS, WATER FOUNTAIN, LAVS, AND WATER CLOSET
 PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 H. AS REQUESTED IN PREVIOUS COMMENTS, THERE ARE TWO
 BRAKE ROOMS AND TWO COFFEE ROOMS THAT ARE NOT SHOWN
 WITH SINKS AND NO CLEAR SPACE FOR ACCESSIBILITY. WOULD
 YOU PLEASE PROVIDE DETAIL FOR THE ONES THAT APPLY PER
 THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 I. THERE SEEMS TO BE A SECOND WATER DRINKING FOUNTAIN
 NEXT TO THE UNISEX RESTROOM, AND THERE IS NO DETAIL
 THAT WILL REQUIRE A CLEAR FLOOR SPACE WITH DIMENSION.
 IF SO, WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 J. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
  
 5. ON SHEET A 402;
  
 A. THERE IS A VERTICAL GRAB BAR, BUT THEY SHALL BE
 INSTALLED IN A HORIZONTAL POSITION PER THE 2020 FBC ACC
 SEC. 609.4.
  
 B. DOOR HARDWARE SHALL BE 34 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. WHERE
 SLIDING DOORS ARE FULLY OPEN, OPERATING HARDWARE SHALL
 BE EXPOSED AND USABLE FROM BOTH SIDES PER THE 2020 FBC
 ACC. SEC. 404.2.7.
  
 C. ON DETAIL E4, THE URINAL IS MISSING; THE HEIGHT
 SHALL BE 17 INCHES SHALL BE A MAXIMUM, AND 13 1/2
 INCHES PER THE 2020 FBC ACC. SEC. 605.2. WOULD YOU
 PLEASE SHOW THE HEIGHT OF THE PARTITION NOT GREATER
 THAN 12 INCHES FROM AND EXTEND NOT LESS THAN 60 INCHES
 PER THE 2020 FBC SEC. P 405.3.5 URINAL PARTITIONS.
  
 D. ON DETAIL E4, THE REFLECTIVE PART OF THE MIRROR
 NEEDS TO BE THE 40 INCHES TO THE REFLECTIVE SIDE FOR
 ONLY THE ACCESSIBLE LAV PER THE 2020 FBC ACC SEC.
 603.3.
  
 E. WOULD YOU, PLEASE SHOW THE GRAB BARS THAT SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER THE
 2020 FBC ACC SEC. 609.4.
  
 F. THE WATER CLOSET IN THE ACCESSIBLE RESTROOM IS
 MEASURED FROM THE UNFINISHED WALL AND SHALL BE TO THE
 CENTERLINE OF THE WATER CLOSET 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL PER THE 2020 FBC ACC.
 SEC. 604.2 LOCATION.
  
 6. 5. ON SHEET A 403;
  
 A. THERE IS A VERTICAL GRAB BAR, BUT THEY SHALL BE
 INSTALLED IN A HORIZONTAL POSITION PER THE 2020 FBC ACC
 SEC. 609.4.
  
 B. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER THE 2020 FBC ACC SEC. 609.4.
  
 C. ON DETAIL, C2 AND C7 SHOW A POWDER RESTROOM THAT MAY
 REQUIRE THE LAV, TOILET, AND GRAB BARS TO BE ACCESSIBLE
 PER THE 2020 FBC ACCESSIBILITY CODE.
  
 D. ON DETAIL A1, THE TOILET DISPENSER SHALL BE 7 INCHES
 MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER PER
 THE 2020 FBC ACC SEC. 604.7.
  
 E. ON DETAIL A5, THE REFLECTIVE PART OF THE MIRROR
 NEEDS TO BE 4 INCHES TO THE REFLECTIVE SIDE PER THE
 2020 FBC ACC SEC. 603.3.
  
 7. ON SHEETS P202, P203, AND P402, THE ICE MAKER AND
 COFFEE MAKER SHALL BE EQUIPPED WITH AN IN-LINE VACUUM
 BREAKER THAT COMPLIES WITH ASSE 1024 PER THE 2020 FBC
 SEC. 608.13.10.
  
 8. ON SHEET P 401, THERE ARE FLOOR DRAINS IN EACH
 RESTROOM AND JANITOR'S ROOM, BUT IT LOOKS LIKE TWO. FOR
 EXAMPLE, THE LADIES ROOMS HAVE TWO FDR LABELED. WOULD
 YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 9. ON SHEET 402 SHOWS THE HOT WATER LINES LOOPED FOR
 THE RECIRCULATING SYSTEM AND ARE NOT IN A CONTINUOUS
 LOOP. THERE ARE REQUIREMENTS IN THE FLORIDA ENERGY CODE
 SEC. C404.6.1. THERE IS A TABLE THAT LIMITS THE
 DISTANCE BETWEEN THE SOURCE AND THE OUTLET. PLEASE
 REFER TO TABLE 405.5.1 FOR THE MAXIMUM ALLOWABLE PIPE
 LENGTH METHOD AND SIZE ACCORDANTLY.
  
 10. ON SHEET P 503;
  
 A. WOULD YOU PLEASE PROVIDE A HAMMER ARRESTOR, WHICH
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED PER THE 2020 FBC SEC. P 604.9.
  
 B. WOULD YOU PLEASE PROVIDE THERMAL EXPANSION CONTROL
 IN THE STORAGE WATER HEATER PER THE 2020 FBC SEC. P
 607.3.
  
 C. IT SHOWS AN OVERFLOW BALANCING VALVE. IS THE DRAIN
 TO A SPECIFIC LOCATION? WOULD YOU PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. THE RECALCULATING PER THE MANUFACTURES SPECIFICATION
 AND MAINTENANCE PURPOSES MAY REQUIRE SHUT-OFF VALVES ON
 EACH SIDE OF THE RECALCULATING PUMP PER THE 2020 FBC
 SEC. 606.2 LOCATION OF SHUTOFF VALVES.
  
 11. ON SHEET P601;
  
 A. DETAIL 1 SHOWS THE PUMP WITH ONE VALVE. WOULD YOU
 PLEASE CORRECT IT PER COMMENT D IN THE PREVIOUS
 COMMENT?
  
 B. THE PRESSURE RELIEF VALVE IS THROUGH A WALL; PLEASE
 CHANGE IT TO DRAIN INTO THE MOP SINK AS SHOWN IN DETAIL
 2 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE SHOW THE THERMAL EXPANSION CONTROL
 IN THE STORAGE WATER HEATER PER THE 2020 FBC SEC. P
 607.3.
  
 12. ON SHEET P602;
  
 A. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS
 FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS.
 PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS FOR THE
 SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
 6. WOULD YOU PLEASE PROVIDE THE UL ASSEMBLY FOR NEW
 WALL PENETRATIONS TO COMPLY WITH THE 2020 FBC CHAPTER
 7.
  
 B. WOULD YOU PLEASE PROVIDE DETAIL FOR THE RIGID
 SUPPORT SWAY BRACING, WHICH SHALL BE PROVIDED AT
 CHANGES IN A DIRECTION MORE SIGNIFICANT THAN 45 DEGREES
 FOR PIPE SIZES 4 INCHES AND LARGER PER FBC-PLUMBING
 SEC. 308.6. SUBMIT DETAILS FOR THE BRACING.
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  