Plan Review Notes
Plan Review Notes For Permit 21080610
Permit Number 21080610
Review Stop M
Sequence Number 1
Notes
Date Text
2021-08-25 10:11:321ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080610
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS MD101 AND MD102 INDICATE 2 NEW EXHAUST DUCTS
 A 10 X 10 AND AN 8 X 8 BUT SHEETS M101 AND M102 SHOW
 ONLY 1 NEW 18 X 8 EXHAUST DUCT CONNECTION TO THE
 EXHAUST DUCT IN THE MECHANICAL ROOM. PLEASE BE
 CONSISTENT. FBC 107.2.1
  
 2) SHEET M101: PLEASE PROVIDE A DETAIL OF THE RETURN
 AIR PATH FROM TENANT SPACE TO THE MECHANICAL ROOM. DO
 THE WALLS BUILT AT THE COFFEE/COPY AREAS GO TO THE
 FLOOR ABOVE? WE MUST MAINTAIN THE RETURN AIR FLOW BACK
 TO THE MECHANICAL ROOM FROM THE TENANT SPACE. FBC
 107.2.1
  
 3) SHEET M102: PLEASE PROVIDE A DETAIL OF THE RETURN
 AIR PATH FROM TENANT SPACE TO THE MECHANICAL ROOM. DO
 THE WALLS BUILT AT THE UNISEX BATHROOM AND OFFICE 2041
 AND THE FILES ROOM AREAS GO TO THE FLOOR ABOVE? WE MUST
 MAINTAIN THE RETURN AIR FLOW BACK TO THE MECHANICAL
 ROOM FROM THE TENANT SPACE. FBC 107.2.1
  
 4) SHEET M102: TOILET ROOM 2050 APPEARS TO HAVE AN
 EXHAUST RATE OF 30 CFM?S? PLEASE SHOW THE CONNECTION
 POINT OF ALL EXHAUST DUCT TO THE EXHAUST PLENUM. FBC
 107.2.1
  
 5) SHEETS M101 AND M102: PLEASE SHOW THE EXHAUST DUCT
 SIZES AND CFM?S FOR EACH BATHROOM. FBC M TABLE
 403.3.1.1
  
 6) SHEET M401: LEVEL 20 RESTROOMS DIAGRAM, PLEASE SHOW
 THE WOMEN?S EXHAUST CFM?S ON THE DRAWING. FBC M TABLE
 403.3.1.1
  
 7) SHEET M701: PLEASE PROVIDE THE BATHROOM EXHAUST FAN
 INFORMATION TO SHOW THE MAX. CFM?S FOR THE FAN. FBC
 107.2.1
  
 8) SHEET M701: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR EACH USE OF SPACE FOR BOTH FLOORS. FBC
 M 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  