| 2021-08-25 16:47:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E-102 |
| | |
| | CONFERENCE ROOM #2012 WALLS OUTLETS MISSING PER |
| | 210.71(B)(1) |
| | |
| | 210.71(B)(1) RECEPTACLE OUTLETS IN FIXED WALLS. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED IN ACCORDANCE |
| | WITH 210.52(A)(1) THROUGH (A)(4). |
| | |
| | PAGE E-101 |
| | |
| | CONFERENCE ROOM #1927 WALLS OUTLETS MISSING PER |
| | 210.71(B)(1) |
| | |
| | 210.71(B)(1) RECEPTACLE OUTLETS IN FIXED WALLS. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED IN ACCORDANCE |
| | WITH 210.52(A)(1) THROUGH (A)(4). |
| | |
| | PAGES E-1-1, AND E102 |
| | |
| | TAMPER RESISTANT OUTLETS REQUIRED BY 406.12(5) MISSING. |
| | |
| | 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND |
| | 20-AMPERE, |
| | 125- AND 250-VOLT NONLOCKING-TYPE RECEPTACLES IN THE |
| | AREAS SPECIFIED IN 406.12(1) THROUGH (7) SHALL BE |
| | LISTED TAMPERRESISTANT RECEPTACLES. |
| | (1) DWELLING UNITS IN ALL AREAS SPECIFIED IN 210.52 AND |
| | 550.13 |
| | (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS |
| | (3) CHILD CARE FACILITIES |
| | (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES |
| | (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE |
| | LIKE IN |
| | CLINICS, MEDICAL AND DENTAL OFFICES AND OUTPATIENT |
| | FACILITIES |
| | (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2 |
| | TO |
| | INCLUDE PLACES OF WAITING TRANSPORTATION, GYMNASIUMS, |
| | SKATING RINKS, AND AUDITORIUMS |
| | (7) DORMITORIES |