| 2021-08-25 11:59:45 | OFFICE BUILDOUT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) DRAWING G002 AND G003 SHOW THE DESIGN PER 2018 IBC - |
| | SHOULD BE 2020 FBC - PLEASE CORRECT. |
| | 2) PLEASE SHOW THE STAIR LANDING DIMENSIONS TO COMPLY |
| | WITH FBC 1011.6 |
| | 3) PLEASE SHOW STAIR RISERS TO COMPLY WITH FBC |
| | 1011.5.5.3 SOLID RISERS. RISERS SHALL BE SOLID. |
| | EXCEPTIONS:(1).SOLID RISERS ARE NOT REQUIRED FOR |
| | STAIRWAYS THAT ARE NOT REQUIRED TO COMPLY WITH SECTION |
| | 1009, PROVIDED THAT THE OPENING BETWEEN TREADS DOES NOT |
| | PERMIT THE PASSAGE OF A SPHERE WITH A DIAMETER OF 4 |
| | INCHES (102 MM). |
| | 4) PLEASE SHOW GLAZED GUARD RAIL AND HANDRAILS TO |
| | COMPLY WITH FBC 2407.1MATERIALS. GLASS USED IN A |
| | HANDRAIL, GUARDRAIL OR GUARD SECTION SHALL BE LAMINATED |
| | GLASS CONSTRUCTED OF FULLY TEMPERED OR |
| | HEAT-STRENGTHENED GLASS AND SHALL COMPLY WITH CATEGORY |
| | II OR CPSC 16 CFR PART 1201 OR CLASS A OF ANSI Z97.1. |
| | GLAZING IN RAILING IN-FILL PANELS SHALL BE OF AN |
| | APPROVED SAFETY GLAZING MATERIAL THAT CONFORMS TO THE |
| | PROVISIONS OF SECTION 2406.1.1. FOR ALL GLAZING TYPES, |
| | THE MINIMUM NOMINAL THICKNESS SHALL BE 1/4 INCH (6.4 |
| | MM). |
| | 5) PLEASE SHOW THE GLAZING IN HAZARDOUS LOCATIONS TO BE |
| | SAFETY GLAZING PER FBC 2406.1. SAFETY GLAZING IS |
| | REQUIRED FOR THE GLAZED LIGHTED WALL AT THE BOTTOM OF |
| | THE STAIR LANDING FBC 2406.4.7 |
| | 6) PLEASE SHOW THE DOOR MANEUVERING CLEARANCE (18" |
| | BESIDE THE LATCH SIDE) FOR THE DOOR AT CORRIDOR 2033 - |
| | FBC A 404.2.4 |
| | 7) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR |
| | DIMENSIONS FROM THE FLOOR TO THE BOTTOM OF THE |
| | "REFLECTIVE SURFACE" FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | 8) DRAWING A403 SHOWS THE MAXIMUM HEIGHT DIMENSION FOR |
| | THE GRAB BAR TO THE CENTER - 36" SHOULD BE THE MAXIMUM |
| | DIMENSION TO THE TOP OF THE GRAB BAR PER FBC A 609.4 |
| | POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, |
| | 9) RESTROOMS IN THE OFFICES NEED TO COMPLY WITH FBC |
| | ACCESSIBILITY FBC 213.2 TOILET ROOMS AND BATHING ROOMS. |
| | WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL |
| | COMPLY WITH 603. |