| Notes |
| Date |
Text |
| 2021-08-26 14:07:35 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE | | | DEPARTMENT, WITH THE FOLLOWING COMMENTS: | | | | | | HYDROSTATIC TESTS. ALL PIPING AND ATTACHED | | | APPURTENANCES SUBJECTED TO SYSTEM WORKING PRESSURE | | | SHALL BE HYDROSTATICALLY TESTED AT 200 PSI (13.8 BAR) | | | AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2 | | | HOURS. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | | | | |
|