| Plan Review Notes For Permit 21080571 |
| Permit Number |
21080571 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-09-10 12:58:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. A GC HAS SUBMITTED AN APPLICATION FOR A SITE | | | LIGHTING PERMIT, WHICH IS TYPICALLY AN ELECTRICAL | | | PERMIT. ONLY ELECTRICAL INFORMATION WAS PROVIDED. FBC B | | | 1609, PROVIDE ENGINEERING FOR THE POLES. THIS PERMIT | | | WILL THEN BE ISSUED AS A COMMERCIAL MISCELLANEOUS | | | PERMIT WITH AN ELECTRICAL SUB. | | | | | | ALTERNATIVELY, THIS CAN REMAIN AN ELECTRICAL PERMIT | | | UPON SUBMISSION OF AN APPLICATION BY A LICENSED | | | ELECTRICAL CONTRACTOR. SUBMISSION OF POLE ENGINEERING | | | CAN BE A DEFERRED SUBMITTAL UPON REQUEST IF THIS | | | REMAINS AN ELECTRICAL PERMIT. | | | | | | 2. THE PERMIT APPLICATION SUBMITTED IS NOT SIGNED. | | | QUALIFIER'S NOTARIZED SIGNATURE REQUIRED. | | | | | | |
|