2021-08-17 15:48:56BUILDING SHELL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE FIRE RATED WALLS AS "FIRE WALLS",
 "FIRE BARRIERS" OR "FIRE PARTITIONS" PER FBC 706, 707,
 708 (DRAWINGS REFER TO "DEMISING WALLS" WHICH ARE NOT
 DEFINED IN THE FBC).
 2) PLEASE SHOW IF TERMITE TREATMENT IS REQUIRED ON
 DRAWING S-300 DETAIL 3 "TRENCHED SLAB IN GRADE INFILL"
 FBC 1816.1.2
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, SOIL AREA DISTURBED AFTER INITIAL CHEMICAL
 SOIL TREATMENT SHALL BE RETREATED WITH A CHEMICAL SOIL
 TREATMENT, INCLUDING SPACES BOXED OR FORMED.
  