| Plan Review Notes For Permit 21080553 |
| Permit Number |
21080553 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-08-17 15:48:56 | BUILDING SHELL ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW THE FIRE RATED WALLS AS "FIRE WALLS", | | | "FIRE BARRIERS" OR "FIRE PARTITIONS" PER FBC 706, 707, | | | 708 (DRAWINGS REFER TO "DEMISING WALLS" WHICH ARE NOT | | | DEFINED IN THE FBC). | | | 2) PLEASE SHOW IF TERMITE TREATMENT IS REQUIRED ON | | | DRAWING S-300 DETAIL 3 "TRENCHED SLAB IN GRADE INFILL" | | | FBC 1816.1.2 | | | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE | | | PREVENTION, SOIL AREA DISTURBED AFTER INITIAL CHEMICAL | | | SOIL TREATMENT SHALL BE RETREATED WITH A CHEMICAL SOIL | | | TREATMENT, INCLUDING SPACES BOXED OR FORMED. | | | |
|