| Date |
Text |
| 2021-09-03 15:49:39 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21080552 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS |
| | BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE |
| | WIND LOAD CALCULATIONS AS REQUIRED. |
| | |
| | 2- REVISE SHUTTERS INSTALLATION SCHEDULE: |
| | A)REVISE TO REFLECT THE REVISED DESIGN PRESSURES. |
| | REVISE DESIGN PRESSURES, ANCHOR SPACING AND EDGE |
| | DISTANCE AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B)MINIMUM EDGE DISTANCE SHOWN. CLEARLY SPECIFY IF THE |
| | EDGE DISTANCE SHOWN INCLUDES THE STUCCO THICKNESS OR |
| | NOT. THIS IS IMPORTANT BECAUSE IN THE FIELD THE ACTUAL |
| | EDGE DISTANCE NEED TO BE LARGER THAN THE ONE SHOWN ON |
| | THE SCHEDULE (TYPICALLY 1/2 MORE TO INCLUDE THE STUCCO |
| | THICKNESS). |
| | NOTE: BASED ON THE OPENING HEIGHT AND THE EDGE DISTANCE |
| | SPECIFIED ON THE INSTALLATION SCHEDULE, IT LOOKS LIKE |
| | THE SPECIFIED SHUTTER SPAN MAY BE TOO SHORT. THE EDGE |
| | DISTANCE IS THE ONE THAT WILL BE VERIFIED IN THE FIELD. |
| | IF TH EDGE DISTANCE IS LESS THAN THE SPECIFIED ONE, |
| | THEN A REVISION WILL BE REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |