| 2021-09-20 22:15:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTES ON PLAN REFERENCE APPLICABLE BUILDING CODE AS |
| | 2014 FBC, CURRENT ADOPTED CODE IS FBC 2020 7TH EDITION. |
| | PROVIDE CORRECTION. |
| | |
| | 2. NOTES ON PLAN REFERENCE APPLICABLE ELECTRICAL CODE |
| | AS 2014 NEC, CURRENT ADOPTED CODE IS NEC 2017 PROVIDE |
| | CORRECTION. |
| | |
| | 3. RECEPTACLES REQUIRED ON BOTH FRONT AND REAR OF |
| | DWELLING OUTSIDE. NEC 210.52E1 |
| | |
| | 4. EQUIPMENT GROUND IS SHOWN FROM METER-CAN TO SERVICE |
| | RATED ATS. EQUIPMENT GROUND ORGINATES AT SERVICE |
| | DISCONNECTING MEANS (ATS). REMOVE EQUIPMENT GROUND FROM |
| | METERCAN TO ATS. NEC 250. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |