2021-09-02 13:54:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080542 632 7TH ST
 MASTER PERMIT 19120513 LOT 8B REVISION
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. MASTER PERMIT 19120513 IS FOR THE SHELL CONSTRUCTION
 OF SIDE B WITH FUTURE TENANT IMPROVEMENT TO BE UNDER A
 SEPARATE PERMIT. THE PROVIDED ARCHITECTURAL PLANS
 INDICATE ONLY UNIT B ON LOT 8 IS UNDER CONSIDERATION.
 THE PLUMBING PLANS ADDRESS UNITS A AND B. IF THE REVIEW
 IS TO BE FOR BOTH SIDES A AND B, THEN ARCHITECTURAL
 PAGES ADDRESSING SIDE A AS WELL AS SIDE B SHALL BE
 SUBMITTED. PER WPB FBC 107.2.1, PLEASE CLARIFY.
 TO BE CLEAR, THE FOLLOWING COMMENTS ADDRESS ONLY THE
 SINGLE TENANT SPACE (8B).
  
 2A. A0.0-8B INDICATES SINGLE TENANT OCCUPANCY TYPE B
 BUT DOES NOT PROVIDE THE SQUARE FOOTAGE OR THE
 OCCUPANCY LOAD. THIS IS REQUIRED TO BE ABLE TO
 DETERMINE THE MINIMUM REQUIRED FACILITIES IN FBC PC
 403. PER WPB FBC 107.2.1, PROVIDE THE SAME.
  
 2B. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 SCHEDULE FOR THE TENANT SPACE NOTING THE REQUIRED
 MINIMUM TOILET FACILITIES AS REQUIRED BY FBC PL 403.3.
  
 3. PER FBC ACC 211.1, WHERE DRINKING FOUNTAINS ARE
 PROVIDED ON AN EXTERIOR SITE, ON A FLOOR, OR WITHIN A
 SECURED AREA THEY SHALL BE PROVIDED IN ACCORDANCE WITH
 211. PER 211.1, NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
 THE SUBMITTED SINGLE DRINKING FOUNTAIN WITH A BOTTLE
 FILLER DOES NOT COMPLY. PER WPB FBC 107.2.1, SCHEDULE
 AND SPECIFY FOR DRINKING FOUNTAIN(S) SHOWING FULL
 COMPLIANCE WITH FBC ACC 602.1 THROUGH 602.7
  
 4. PER FBC ACC 212.3, HAND SINK SHALL COMPLY WITH FBC
 ACC 606.3 WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES/2 FEET 10 INCHES MAXIMUM (NOT
 35 INCHES/2 FEET 11 INCHES AS SHOWN, SEE PLAN SHEET
 A2.0C) ABOVE THE FINISH FLOOR OR GROUND. ADDITIONALLY
 SHOW TOE AND KNEE CLEARANCE AND CLEAR FLOOR SPACE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
  
 5. PER WPB FBC 107.2.1, SHOW PROVIDE WALL FINISH FOR
 THE MOP SINK SHOWING COMPLIANCE WITH FBC PL 310.3 AND
 FBC 1210.2.2. WALLS AND PARTITIONS WITHIN 2 FEET (610
 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. PLEASE NOTE THAT FBC 1210.2.2
 STIPULATES THAT THE MATERIAL BE "HARD." THE INTENT OF
 THIS SECTION IS THAT THE SURROUNDING MATERIAL SHOULD
 NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH THAT THE
 MATERIAL COULD BECOME ABSORBENT AND THUS, NOT READILY
 CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN WHERE
 COATED WITH HIGHLY DURABLE PAINTS SUCH AS EPOXY, DOES
 NOT MEET THE INTENT OF SECTION 1210.2.2. THE TYPICAL
 MATERIALS USED FOR THIS APPLICATION ARE CERAMIC TILE,
 FIBERGLASS REINFORCED PLASTIC (FRP) PANELS, PHENOLIC
 PANELS, LAMINATED PLASTIC PANELS, PAINTED STEEL AND
 STAINLESS STEEL.
  
 6A. PLEASE NOTE THAT PER FBC PL 403.3, CUSTOMERS,
 PATRONS AND VISITORS SHALL BE PROVIDED WITH PUBLIC
 TOILET FACILITIES IN STRUCTURES AND TENANT SPACES
 INTENDED FOR PUBLIC UTILIZATION. THE NUMBER OF PLUMBING
 FIXTURES LOCATED WITHIN THE REQUIRED TOILET FACILITIES
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 403 FOR
 ALL USERS. EMPLOYEES SHALL BE PROVIDED WITH TOILET
 FACILITIES IN ALL OCCUPANCIES. EMPLOYEE TOILET
 FACILITIES SHALL BE EITHER SEPARATE OR COMBINED
 EMPLOYEE AND PUBLIC TOILET FACILITIES. EXCEPTION:
 PUBLIC TOILET FACILITIES SHALL NOT BE REQUIRED IN:
 ....OPEN OR ENCLOSED PARKING GARAGES WHERE THERE ARE NO
 PARKING ATTENDANTS.
 ....STRUCTURES AND TENANT SPACES INTENDED FOR QUICK
 TRANSACTIONS, INCLUDING TAKEOUT, PICKUP AND DROP-OFF,
 HAVING A PUBLIC ACCESS AREA LESS THAN OR EQUAL TO 300
 SQUARE FEET (28 M2).
  
 6B. PER FBC PL 403.3, PROVIDE MINIMUM TOILET FACILITIES
 AS REQUIRED BY FBC PL 403.3. IT IS NOTED THAT A FUTURE
 TOILET ROOM IS INDICATED IN THE STORAGE ROOM. PER WPB
 FBC 107.2.1, PROVIDE ROUGH-IN PLUMBING FOR LAVATORY AS
 WELL AS THE WATER CLOSET. INCLUDE IN PLAN VIEW AND
 ISOMETRIC. AS NOTED IN FBC PL CHAPTER 2, DEFINITIONS,
 ROUGH-IN INCLUDES ALL PARTS OF THE PLUMBING SYSTEM THAT
 ARE INSTALLED PRIOR TO THE INSTALLATION OF FIXTURES.
 THIS INCLUDES DRAINAGE, WATER SUPPLY, VENT PIPING AND
 THE NECESSARY FIXTURE SUPPORTS (I INTERPRET THIS TO
 INCLUDE BACKING FOR GRAB BARS AS WELL AS FOR POSSIBLE
 WALL HUNG LAVATORIES) AND ANY FIXTURES THAT ARE BUILT
 INTO THE STRUCTURE.
 NOTE: HAND SINK SHALL NOT BE USED TO WET VENT WATER
 CLOSET; FBC PL 912.1.
  
 6C. RE: A2.0C; STORAGE ROOM NOTE 1 STATES GC TO PROVIDE
 ROUGH PLUMBING LINES IN STORAGE ROOM FOR FUTURE WATER
 CLOSET USE. NOTE SHALL BE AMENDED TO STATE GC TO
 PROVIDE ROUGH-IN PLUMBING LINES AND GRAB BAR BACKING IN
 STORAGE ROOM TO MAKE PROVISION FOR FUTURE RESTROOM TO
 BE COMPLETED BY FUTURE TENANT UNDER A SEPARATE PERMIT.
 PER WPB FBC 107.2.1, PROVIDE ACTUAL STORAGE ROOM
 DIMENSIONS, FIXTURE CENTERLINE DIMENSIONS AND GRAB BAR
 BACKING MATERIAL, DIMENSIONS (HORIZONTAL AND VERTICAL)
 TO SHOW COMPLIANCE WITH FBC ACC CHAPTERS 2, 3 AND 6 CAN
 BE ACCOMPLISHED.
  
 7. RE: P000 PLUMBING GENERAL NOTE 30; CODE REFERENCE
 FBC-P 6017.1 IS NOT VALID. REFERENCE SHOULD BE FBC-P
 607.1, 607.1.1 AND 607.1.2; TEXT NOTE SHALL ALSO
 INCLUDE A REFERENCE TO FBC-P 424.3 REQUIRING INDIVIDUAL
 SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. PER WPB FBC 107.2.1,
 PLEASE REVISE THE NOTE ACCORDINGLY.
  
 8. RE: P301 (AND P401) PLUMBING NOTE 8; PER WPB FBC
 107.2.1, PROVIDE SPECIFICATION AND DETAIL FOR NOTED
 FIRE BLOCKING FOR PIPES PASSING THROUGH NOTED WALLS AND
 FLOOR. (NOTED THAT STRUCTURE IS WOOD FRAMED)
  
 9. PER WPB FBC 107.2.1, PROVIDE DETAIL AND
 SPECIFICATION FOR RODENT PROOFING OF FLOOR PIPE AND
 OTHER PLUMBING PENETRATIONS THROUGH THE FLOOR. SEE FBC
 PL 301.1 THROUGH 304.4.
  
 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 SHOWING HOW PIPING WILL BE HUNG FROM WOODEN FLOOR
 JOISTS AND ROOF RAFTERS WITH A NOTE STATING,
 "HORIZONTAL PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH
 FBC PL TABLE 308.5."
  
 11. WATER HEATER SCHEDULE & DETAIL- PROVIDE DETAIL OF
 WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING
 INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE
 IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL
 DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING
 TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL
 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6,
 504.7, 504.7.1 AND 504.7.2. RE: P701/DETAIL 5; WATER
 HEATER DETAIL. PROVIDE THERMAL EXPANSION DEVICE
 COMPLYING WITH FBC PL 607.3
 ...A)EXPANSION TANK IS SCHEDULED WITH INSTRUCTIONS FOR
 INSTALLATION ON P801.
 ...B)PER WPB FBC 107.2.1, PLEASE AMEND NOTE A IN THE
 EXPANSION TANK SCHEDULE TO NOTE ?EXPANSION TANK BE
 CONNECTED TO THE WATER HEATER COLD WATER SUPPLY PIPE AT
 A POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES,
 PRESSURE REDUCING VALVES AND BACKFLOW PREVENTERS?,
 COMPLYING WITH FBC PL 607.3.
 ...C) PER WPB FBC 107.2.1, SHOW LOCATION OF SCHEDULED
 EXPANSION TANK. THIS MAY EASILY BE ACCOMPLISHED BY
 SHOWING IT ON P701/DETAIL 5; WATER HEATER DETAIL.
  
 12. RE: P701/DETAIL 5; WATER HEATER DETAIL. DETAIL
 INDICATES CONCRETE ANCHORS FOR WALL MOUNTED WATER
 HEATER SUPPORT. A2.0B ENLARGED FLOOR PLANS INDICATE
 METAL FRAMED PARTITIONS, NOT CONCRETE WALLS. PER WPB
 FBC 107.2.1, CLARIFY AND CORRECT AS NECESSARY.
  
 13. P701 DETAILS INDICATE CONCRETE SLAB ON GRADE.
 ACTUAL STRUCTURE IS WOOD FRAMED JOISTS AND BEAMS. PER
 WPB FBC 107.2.1, PROVIDE DETAIL(S) FOR INTERIOR
 PENETRATIONS THAT REFLECT THE ACTUAL CONSTRUCTION.
 PLEASE NOTE, ECOS NOTED ON P301 AND P601 ARE SHOWN AS
 FLOOR CLEANOUTS, NOT WALL CLEANOUTS AS INDICATED FOR
 INTERIOR CLEANOUT DETAIL. PER WPB FBC 107.2.1, PROVIDE
 A DETAIL FOR ECO AND INCLUDE IN PLUMBING SCHEDULE. IF
 ECO IS ACTUALLY ROUGH PLUMBING FOR A FUTURE WATER
 CLOSET, THEN PROVIDE A VENT FOR IT. PLEASE NOTE THAT
 THE HAND SINK FOR THE BREAK ROOM DOES NOT CONSTITUTE A
 LEGITIMATE WET VENT AS DETAILED IN FBC PL 912.1 AS IT
 DOES NOT QUALIFY AS A BATHROOM GROUP FIXTURE (SEE FBC
 PL CHAPTER 2, DEFINITIONS). ADDITIONALLY, PROVISIONS
 NEED TO BE MADE FOR THE REQUIRED LAVATORY.
  
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21080542 632 7TH ST
 MASTER PERMIT 19120513 LOT 8B REVISION
  