| 2022-04-11 14:07:27 | 1ST REVIEW FMC | | | PERMIT: 21080540 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS APPEARS TO BE A REVISION TO A SHELL PERMIT? | | | THERE WAS NO MECHANICAL SUBMITTED FOR THE SHELL PERMIT | | | 19120512. PROVIDE THE ENERGY CALCULATIONS AND THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THIS NEW | | | BUILDING. FBC 107.2.1 | | | | | | 2) SHEET M801 APPEARS TO INCLUDE MULTIPLE AHU?S AND | | | EXHAUST FANS. THE MECHANICAL SHEET M301 ONLY INDICATES | | | AHU-1, EF-1 AND EF-2. PLEASE REMOVE ALL OTHER UNITS | | | THAT DO NOT BELONG WITH THIS UNIT. | | | | | | 3) THE REVISION FORM DOES NOT INCLUDE THE VALUE OF THIS | | | REVISION. THERE CLEARLY IS A VALUE TO THIS MECHANICAL | | | SYSTEM THAT WAS NOT INCLUDED IN THE SHELL PERMIT. | | | PLEASE SHOW THE ACCURATE VALUE FOR THIS MECHANICAL | | | SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|