Plan Review Notes
Plan Review Notes For Permit 21080540
Permit Number 21080540
Review Stop M
Sequence Number 1
Notes
Date Text
2022-04-11 14:07:271ST REVIEW FMC
 PERMIT: 21080540
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS APPEARS TO BE A REVISION TO A SHELL PERMIT?
 THERE WAS NO MECHANICAL SUBMITTED FOR THE SHELL PERMIT
 19120512. PROVIDE THE ENERGY CALCULATIONS AND THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THIS NEW
 BUILDING. FBC 107.2.1
  
 2) SHEET M801 APPEARS TO INCLUDE MULTIPLE AHU?S AND
 EXHAUST FANS. THE MECHANICAL SHEET M301 ONLY INDICATES
 AHU-1, EF-1 AND EF-2. PLEASE REMOVE ALL OTHER UNITS
 THAT DO NOT BELONG WITH THIS UNIT.
  
 3) THE REVISION FORM DOES NOT INCLUDE THE VALUE OF THIS
 REVISION. THERE CLEARLY IS A VALUE TO THIS MECHANICAL
 SYSTEM THAT WAS NOT INCLUDED IN THE SHELL PERMIT.
 PLEASE SHOW THE ACCURATE VALUE FOR THIS MECHANICAL
 SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  