| 2022-03-17 13:43:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21080539 628 7TH ST |
| | MASTER PERMIT 19120511 LOT 7B REVISION |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | |
| | 1. SECOND REQUEST: PER FBC ACC 211.1, WHERE DRINKING |
| | FOUNTAINS ARE PROVIDED ON AN EXTERIOR SITE, ON A FLOOR, |
| | OR WITHIN A SECURED AREA THEY SHALL BE PROVIDED IN |
| | ACCORDANCE WITH 211. PER 211.1, NO FEWER THAN TWO |
| | DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | TO BE CLEAR, THE SUBMITTED SINGLE DRINKING FOUNTAIN |
| | WITH A BOTTLE FILLER DOES NOT COMPLY WITH FBC PL 602.4 |
| | (MAXIMUM SPOUT HEIGHT 36 INCHES ABOVE THE FLOOR FOR |
| | WHEELCHAIR ACCESSIBILITY) AND 602.7 (MINIMUM SPOUT |
| | HEIGHT 38 INCHES ABOVE THE FLOOR FOR STANDING PERSONS); |
| | A2.0C/DETAIL 3 SHOWS SPOUT HEIGHT AT 37 -1/2 INCHES |
| | ABOVE THE FLOOR. PER WPB FBC 107.2.1, SCHEDULE AND |
| | SPECIFY FOR DRINKING FOUNTAIN(S) SHOWING FULL |
| | COMPLIANCE WITH FBC ACC 602.1 THROUGH 602.7. PLEASE |
| | CONTACT ROBERT BROWN, BUILDING OFFICIAL AT 561-805-6652 |
| | WITH ANY QUESTION OR CONCERNS. |
| | |
| | 2.ORIGINAL COMMENT: PER FBC ACC 212.3, HAND SINK SHALL |
| | COMPLY WITH FBC ACC 606.3 WITH THE FRONT OF THE HIGHER |
| | OF THE RIM OR COUNTER SURFACE 34 INCHES/2 FEET 10 |
| | INCHES MAXIMUM (NOT 35 INCHES/2 FEET 11 INCHES AS |
| | SHOWN, SEE PLAN SHEET A2.0C) ABOVE THE FINISH FLOOR OR |
| | GROUND. ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AND |
| | CLEAR FLOOR SPACE AS REQUIRED BY FBC ACC 306.2 AND |
| | 306.3. |
| | NEW COMMENT: PER WPB FBC 107.2.1, PLEASE SHOW THE |
| | TURNING SPACE IN THE BREAKROOM COMPLYING WITH FBC ACC |
| | 304.3.1 OR 304.3.2. SHOW THAT THE BREAKROOM SINK AND |
| | CABINET AS DESIGNED WILL NOT INTERFERE WITH THE TURNING |
| | SPACE. |
| | NEW COMMENT: REGARDING THE HAND SINK; FBC ACC 804.3.1, |
| | REQUIRES THE CLEAR FLOOR SPACE TO BE CENTERED ON THE |
| | KITCHEN WORK SURFACE, WHILE THIS IS DIRECTED AT |
| | KITCHENS AND KITCHENETTES REQUIRING A FORWARD APPROACH, |
| | IT APPEARS THAT A PERSON OPERATING A WHEELCHAIR WOULD |
| | BE HARD PRESSED TO COMFORTABLY ACCESS THE CONTROLS OF |
| | THE HAND SINK. PLEASE REVIEW FBC ACC 308 AND 309. |
| | CONSIDER PROVIDING A FORWARD APPROACH WITH KNEE AND TOE |
| | CLEARANCE. |
| | |
| | 3. SECOND REQUEST: SEE ORIGINAL COMMENT 9. ARCHITECT |
| | AND MEP EACH ASSIGNED COMMENT TO THE OTHER WITH NO |
| | RESOLUTION. PER WPB FBC 107.2.1, PROVIDE DETAIL AND |
| | SPECIFICATION FOR RODENT PROOFING OF FLOOR PIPE AND |
| | OTHER PLUMBING PENETRATIONS THROUGH THE FLOOR. SEE FBC |
| | PL 301.1 THROUGH 304.4. |
| | |
| | 4.SECOND REQUEST: P701/DETAIL 5; WATER HEATER DETAIL. |
| | DETAIL INDICATES CONCRETE ANCHORS FOR WALL MOUNTED |
| | WATER HEATER SUPPORT. A2.0B ENLARGED FLOOR PLANS |
| | INDICATE METAL FRAMED PARTITIONS, NOT CONCRETE WALLS. |
| | PER WPB FBC 107.2.1, CLARIFY AND CORRECT AS NECESSARY. |
| | |
| | 5. NEW COMMENT: WATER HEATER SCHEDULE CALLS FOR A.O. |
| | SMITH MODEL DSE-30A-240V/SGL PH/6KW. PRODUCT DATA NOTES |
| | 30 TO 120 GALLON UNITS ARE NOT AVAILABLE WITH LESS THAN |
| | 12.3KW. PER WPB FBC 107.2.1, PLEASE CLARIFY. |
| | |
| | 6. NEW COMMENT: P601/SANITARY ISOMETRIC; PER FBC PL |
| | 1002.1, PROVIDE A TRAP FOR THE MOP SINK. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |