Plan Review Notes
Plan Review Notes For Permit 21080539
Permit Number 21080539
Review Stop P
Sequence Number 2
Notes
Date Text
2022-03-17 13:43:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080539 628 7TH ST
 MASTER PERMIT 19120511 LOT 7B REVISION
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
  
 1. SECOND REQUEST: PER FBC ACC 211.1, WHERE DRINKING
 FOUNTAINS ARE PROVIDED ON AN EXTERIOR SITE, ON A FLOOR,
 OR WITHIN A SECURED AREA THEY SHALL BE PROVIDED IN
 ACCORDANCE WITH 211. PER 211.1, NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
 TO BE CLEAR, THE SUBMITTED SINGLE DRINKING FOUNTAIN
 WITH A BOTTLE FILLER DOES NOT COMPLY WITH FBC PL 602.4
 (MAXIMUM SPOUT HEIGHT 36 INCHES ABOVE THE FLOOR FOR
 WHEELCHAIR ACCESSIBILITY) AND 602.7 (MINIMUM SPOUT
 HEIGHT 38 INCHES ABOVE THE FLOOR FOR STANDING PERSONS);
 A2.0C/DETAIL 3 SHOWS SPOUT HEIGHT AT 37 -1/2 INCHES
 ABOVE THE FLOOR. PER WPB FBC 107.2.1, SCHEDULE AND
 SPECIFY FOR DRINKING FOUNTAIN(S) SHOWING FULL
 COMPLIANCE WITH FBC ACC 602.1 THROUGH 602.7. PLEASE
 CONTACT ROBERT BROWN, BUILDING OFFICIAL AT 561-805-6652
 WITH ANY QUESTION OR CONCERNS.
  
 2.ORIGINAL COMMENT: PER FBC ACC 212.3, HAND SINK SHALL
 COMPLY WITH FBC ACC 606.3 WITH THE FRONT OF THE HIGHER
 OF THE RIM OR COUNTER SURFACE 34 INCHES/2 FEET 10
 INCHES MAXIMUM (NOT 35 INCHES/2 FEET 11 INCHES AS
 SHOWN, SEE PLAN SHEET A2.0C) ABOVE THE FINISH FLOOR OR
 GROUND. ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AND
 CLEAR FLOOR SPACE AS REQUIRED BY FBC ACC 306.2 AND
 306.3.
 NEW COMMENT: PER WPB FBC 107.2.1, PLEASE SHOW THE
 TURNING SPACE IN THE BREAKROOM COMPLYING WITH FBC ACC
 304.3.1 OR 304.3.2. SHOW THAT THE BREAKROOM SINK AND
 CABINET AS DESIGNED WILL NOT INTERFERE WITH THE TURNING
 SPACE.
 NEW COMMENT: REGARDING THE HAND SINK; FBC ACC 804.3.1,
 REQUIRES THE CLEAR FLOOR SPACE TO BE CENTERED ON THE
 KITCHEN WORK SURFACE, WHILE THIS IS DIRECTED AT
 KITCHENS AND KITCHENETTES REQUIRING A FORWARD APPROACH,
 IT APPEARS THAT A PERSON OPERATING A WHEELCHAIR WOULD
 BE HARD PRESSED TO COMFORTABLY ACCESS THE CONTROLS OF
 THE HAND SINK. PLEASE REVIEW FBC ACC 308 AND 309.
 CONSIDER PROVIDING A FORWARD APPROACH WITH KNEE AND TOE
 CLEARANCE.
  
 3. SECOND REQUEST: SEE ORIGINAL COMMENT 9. ARCHITECT
 AND MEP EACH ASSIGNED COMMENT TO THE OTHER WITH NO
 RESOLUTION. PER WPB FBC 107.2.1, PROVIDE DETAIL AND
 SPECIFICATION FOR RODENT PROOFING OF FLOOR PIPE AND
 OTHER PLUMBING PENETRATIONS THROUGH THE FLOOR. SEE FBC
 PL 301.1 THROUGH 304.4.
  
 4.SECOND REQUEST: P701/DETAIL 5; WATER HEATER DETAIL.
 DETAIL INDICATES CONCRETE ANCHORS FOR WALL MOUNTED
 WATER HEATER SUPPORT. A2.0B ENLARGED FLOOR PLANS
 INDICATE METAL FRAMED PARTITIONS, NOT CONCRETE WALLS.
 PER WPB FBC 107.2.1, CLARIFY AND CORRECT AS NECESSARY.
  
 5. NEW COMMENT: WATER HEATER SCHEDULE CALLS FOR A.O.
 SMITH MODEL DSE-30A-240V/SGL PH/6KW. PRODUCT DATA NOTES
 30 TO 120 GALLON UNITS ARE NOT AVAILABLE WITH LESS THAN
 12.3KW. PER WPB FBC 107.2.1, PLEASE CLARIFY.
  
 6. NEW COMMENT: P601/SANITARY ISOMETRIC; PER FBC PL
 1002.1, PROVIDE A TRAP FOR THE MOP SINK.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  