2022-03-21 08:05:55THIS APPEARS TO BE THE SAME INFORMATION AS PERMIT
 #21080542
  
 PLEASE REMOVE THE AHU-1 FROM THE ENERGY CALCULATIONS AS
 THIS WILL BE INSTALLED UNDER A SEPARATE PERMIT
 ACCORDING TO SHEET M301 NOTE.
 PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 TENANT SPACE.
  