Plan Review Notes
Plan Review Notes For Permit 21080537
Permit Number 21080537
Review Stop P
Sequence Number 2
Notes
Date Text
2022-06-02 15:01:51WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080537 626 7TH ST
 MASTER 19120504 LOT 7A REVISION
  
 SIGNATURES FOR PLUMBING; ELECTRONIC SIGNATURES APPEAR
 TO BE SCANNED. CORRECTIONS NEEDED. IN LIEU OF VALID
 ELECTRONIC SIGNATURE, A PHYSICAL SET OF APPROVED PLANS
 SIGNED, DATED AND SEALED BY THE DESIGNER AS REQUIRED BY
 FAC 61G15-23.001 SHALL BE PROVIDED TO THE BUILDING
 DEPARTMENT PRIOR TO ISSUANCE OF PERMIT. JS
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 ***A) COMPLIED
 ***B) SECOND REQUEST: PER FBC 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY & DRAINPIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT.
 ARCHITECT RESPONSE: NOTES HAVE BEEN REVISED TO REQUIRE
 G.C. TO PROVIDE INSULATION FOR DRAIN PIPE BELOW
 LAVATORY. PLEASE SEE SHEET A2.0B NOTES C8 & ELEVATION
 DETAIL 5 & 2
 NEW COMMENT:
 0001) NOTE C8 IS NOT ON THE PLAN
 0002) DETAIL 5 & 2 DO NOT MENTION INSULATION
  
 ***C) SECOND REQUEST: MIRRORS LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE "REFLECTING" SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
 ARCHITECT RESPONSE: THIS ADJUSTMENT HAS BEEN PROVIDED
 WITHIN REVISION 6. THE MIRRORS DIMENSION FROM THE FLOOR
 TO THE REFLECTIVE SURFACE IS 40 INCHES. PLEASE SEE
 SHEET A2.0B DETAIL ELEVATION 5
 DIMENSION SHOWN IS CLEARLY TO BOTTOM OF APPARENT FRAME.
 PLEASE ADD THE WORDS "REFLECTING SURFACE" TO CLARIFY.
  
 2. SECOND REQUEST:
 BREAK ROOM SINK: NEW COMMENT: FBC ACC 804.3.1, REQUIRES
 THE CLEAR FLOOR SPACE TO BE CENTERED ON THE KITCHEN
 WORK SURFACE, WHILE THIS IS DIRECTED AT KITCHENS AND
 KITCHENETTES REQUIRING A FORWARD APPROACH, IT APPEARS
 THAT A PERSON OPERATING A WHEELCHAIR WOULD BE HARD
 PRESSED TO COMFORTABLY ACCESS THE CONTROLS OF THE HAND
 SINK WITH A SIDE APPROACH THAT DOES NOT CENTER ON THE
 FIXTURE. PLEASE REVIEW FBC ACC 308 AND 309. CONSIDER
 PROVIDING A FORWARD APPROACH WITH KNEE AND TOE
 CLEARANCE.
 NO RESPONSE FROM ARCHITECT. PLEASE ACKNOWLEGE AND
 PROVIDE A RESPONSE.
  
 3. COMPLIED
  
 4. COMPLIED
  
 5. N/A
  
 6. P801: REGARDING THE PLUMBING FIXTURE SCHEDULE
 COMMENT REFERRING TO ARCHITECT, OWNERSHIP OR INTERIOR
 DESIGN FOR SELECTION OF ALL FIXTURES AND ACCESSORIES,
 PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUALS FOR ALL SCHEDULED
 PLUMBING FIXTURES AND ACCESSORIES.
 ARCHITECT RESPONSE: PLEASE SEE ATTACHED FOR
 MANUFACTURER'S SPECIFICATIONS FOR PLUMBING FIXTURES
 NEW COMMENT: WATER CLOSET, LAVATORY, FAUCET AND BOTTLE
 TRAP ARE SHOWN ON A2.0B. HOWEVER, THE LAVATORY IS NOT
 INCLUDED IN THE ATTACHMENTS (SUPPORTING DOCUMENTS)
 NEW COMMENT: BOTTLE TRAP- SEE FBC PL 1002.3(4) AND FBC
 PL 412.1.2. PROVIDE IN MANUFACTURER?S
 SPECIFICATION/DOCUMENTATION, THE MANUFACTURING
 STANDARD(S) THE PRODUCT COMPLIES WITH
 EXAMPLE: KOHLER K-9033 BOTTLE TRAP SPEC SHEET SHOWS
 COMPLIANCE WITH ASME A112.18.2/CSA B125.2
  
 4. COMPLIED
  
 5. COMPLIED
  
 6. COMPLIED
  
 7. COMPLIED
  
 8. NOT IN THIS PERMIT
  
 9. NOT IN THIS PERMIT
  
 10. NOT IN THIS PERMIT
  
 11. COMPLIED
  
 12. NEW COMMENT: REGARDING THE SUBMITTED GREASE TRAP
 PLAN UPLOADED TO SUPPORTING DOCUMENTS, PLEASE NOTE THAT
 THE DOCUMENT MUST BE DATED, SIGNED AND SEALED BY THE
 DESIGNER AS REQUIRED BY CHAPTER 471 FS & 61G15 FAC OR
 481 FS & 61G1 FAC
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
  
  