| | 21080537 626 7TH ST |
| | MASTER 19120504 LOT 7A REVISION |
| | |
| | SIGNATURES FOR PLUMBING; ELECTRONIC SIGNATURES APPEAR |
| | TO BE SCANNED. CORRECTIONS NEEDED. IN LIEU OF VALID |
| | ELECTRONIC SIGNATURE, A PHYSICAL SET OF APPROVED PLANS |
| | SIGNED, DATED AND SEALED BY THE DESIGNER AS REQUIRED BY |
| | FAC 61G15-23.001 SHALL BE PROVIDED TO THE BUILDING |
| | DEPARTMENT PRIOR TO ISSUANCE OF PERMIT. JS |
| | |
| | 2ND REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOM INDICATING THE FOLLOWING: |
| | ***A) COMPLIED |
| | ***B) SECOND REQUEST: PER FBC 606.5 EXPOSED PIPES AND |
| | SURFACES. WATER SUPPLY & DRAINPIPES UNDER LAVATORIES |
| | AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. |
| | ARCHITECT RESPONSE: NOTES HAVE BEEN REVISED TO REQUIRE |
| | G.C. TO PROVIDE INSULATION FOR DRAIN PIPE BELOW |
| | LAVATORY. PLEASE SEE SHEET A2.0B NOTES C8 & ELEVATION |
| | DETAIL 5 & 2 |
| | NEW COMMENT: |
| | 0001) NOTE C8 IS NOT ON THE PLAN |
| | 0002) DETAIL 5 & 2 DO NOT MENTION INSULATION |
| | |
| | ***C) SECOND REQUEST: MIRRORS LOCATED ABOVE LAVATORIES |
| | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| | OF THE "REFLECTING" SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND PER FBC ACC 603.3. |
| | ARCHITECT RESPONSE: THIS ADJUSTMENT HAS BEEN PROVIDED |
| | WITHIN REVISION 6. THE MIRRORS DIMENSION FROM THE FLOOR |
| | TO THE REFLECTIVE SURFACE IS 40 INCHES. PLEASE SEE |
| | SHEET A2.0B DETAIL ELEVATION 5 |
| | DIMENSION SHOWN IS CLEARLY TO BOTTOM OF APPARENT FRAME. |
| | PLEASE ADD THE WORDS "REFLECTING SURFACE" TO CLARIFY. |
| | |
| | 2. SECOND REQUEST: |
| | BREAK ROOM SINK: NEW COMMENT: FBC ACC 804.3.1, REQUIRES |
| | THE CLEAR FLOOR SPACE TO BE CENTERED ON THE KITCHEN |
| | WORK SURFACE, WHILE THIS IS DIRECTED AT KITCHENS AND |
| | KITCHENETTES REQUIRING A FORWARD APPROACH, IT APPEARS |
| | THAT A PERSON OPERATING A WHEELCHAIR WOULD BE HARD |
| | PRESSED TO COMFORTABLY ACCESS THE CONTROLS OF THE HAND |
| | SINK WITH A SIDE APPROACH THAT DOES NOT CENTER ON THE |
| | FIXTURE. PLEASE REVIEW FBC ACC 308 AND 309. CONSIDER |
| | PROVIDING A FORWARD APPROACH WITH KNEE AND TOE |
| | CLEARANCE. |
| | NO RESPONSE FROM ARCHITECT. PLEASE ACKNOWLEGE AND |
| | PROVIDE A RESPONSE. |
| | |
| | 3. COMPLIED |
| | |
| | 4. COMPLIED |
| | |
| | 5. N/A |
| | |
| | 6. P801: REGARDING THE PLUMBING FIXTURE SCHEDULE |
| | COMMENT REFERRING TO ARCHITECT, OWNERSHIP OR INTERIOR |
| | DESIGN FOR SELECTION OF ALL FIXTURES AND ACCESSORIES, |
| | PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S |
| | SPECIFICATION/INSTALLATION MANUALS FOR ALL SCHEDULED |
| | PLUMBING FIXTURES AND ACCESSORIES. |
| | ARCHITECT RESPONSE: PLEASE SEE ATTACHED FOR |
| | MANUFACTURER'S SPECIFICATIONS FOR PLUMBING FIXTURES |
| | NEW COMMENT: WATER CLOSET, LAVATORY, FAUCET AND BOTTLE |
| | TRAP ARE SHOWN ON A2.0B. HOWEVER, THE LAVATORY IS NOT |
| | INCLUDED IN THE ATTACHMENTS (SUPPORTING DOCUMENTS) |
| | NEW COMMENT: BOTTLE TRAP- SEE FBC PL 1002.3(4) AND FBC |
| | PL 412.1.2. PROVIDE IN MANUFACTURER?S |
| | SPECIFICATION/DOCUMENTATION, THE MANUFACTURING |
| | STANDARD(S) THE PRODUCT COMPLIES WITH |
| | EXAMPLE: KOHLER K-9033 BOTTLE TRAP SPEC SHEET SHOWS |
| | COMPLIANCE WITH ASME A112.18.2/CSA B125.2 |
| | |
| | 4. COMPLIED |
| | |
| | 5. COMPLIED |
| | |
| | 6. COMPLIED |
| | |
| | 7. COMPLIED |
| | |
| | 8. NOT IN THIS PERMIT |
| | |
| | 9. NOT IN THIS PERMIT |
| | |
| | 10. NOT IN THIS PERMIT |
| | |
| | 11. COMPLIED |
| | |
| | 12. NEW COMMENT: REGARDING THE SUBMITTED GREASE TRAP |
| | PLAN UPLOADED TO SUPPORTING DOCUMENTS, PLEASE NOTE THAT |
| | THE DOCUMENT MUST BE DATED, SIGNED AND SEALED BY THE |
| | DESIGNER AS REQUIRED BY CHAPTER 471 FS & 61G15 FAC OR |
| | 481 FS & 61G1 FAC |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | |
| | |