| Plan Review Notes For Permit 21080535 |
| Permit Number |
21080535 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-11 16:50:50 | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATION STATES | | | STYX ALLEY & 7TH STREET LOT 6, THERE ARE 2 STRUCTURES | | | ON LOT 6. THE SUBMITTED DRAWINGS INDICATE THEY ARE FOR | | | LOT 6A. PLEASE LABEL THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THE CORRECT STRUCTURE ON THE LOT. | | | | | | 2) THIS APPEARS TO BE A REVISION TO A SHELL PERMIT? | | | THERE WAS NO MECHANICAL SUBMITTED FOR THE SHELL PERMIT | | | 19120512. PROVIDE THE ENERGY CALCULATIONS AND THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THIS NEW | | | BUILDING. FBC 107.2.1 | | | | | | 3) THE REVISION FORM DOES NOT INCLUDE THE VALUE OF THIS | | | REVISION. THERE CLEARLY IS A VALUE TO THIS MECHANICAL | | | SYSTEM THAT WAS NOT INCLUDED IN THE SHELL PERMIT. | | | PLEASE SHOW THE ACCURATE VALUE FOR THIS MECHANICAL | | | SYSTEM. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|