| 2022-03-31 12:42:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21080534 620 7TH ST |
| | MASTER PERMIT 19120500 LOT 5B REVISION |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. NEW COMMENT: DUE TO A CHANGE IN PROCESS, THE |
| | BACKFLOW PERMIT AND GREASE INTERCEPTOR PERMITS ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2.NEW COMMENT: GREASE INTERCEPTOR; PLEASE NOTE THAT PER |
| | FBC PL 301.7 AND 303.2, THE INSTALLATION OF THE SCHIER |
| | GB-75 GREASE INTERCEPTOR SHALL CONFORM TO A MINIMUM OF |
| | THE MANUFACTURER'S RECOMMENDATIONS. IN ACCORDANCE WITH |
| | THE GB-75 INSTALLATION GUIDE PAGE 8, 9 AND 10 OF 10, A |
| | TWO-WAY CLEANOUT IS REQUIRED ON BOTH THE INLET AND |
| | OUTLET SIDE OF THE GREASE INTERCEPTOR. |
| | |
| | 3.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE DETAIL |
| | FOR TIEDOWN OF TANK. PROVIDE DETAIL OF BURIED TANK. |
| | PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF |
| | EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE |
| | FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. SEE THE |
| | FOLLOWING: |
| | ***A) PLEASE NOTE THAT PER FBC PL 301.7 AND 303.2, THE |
| | INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR |
| | SHALL CONFORM TO A MINIMUM OF THE MANUFACTURER'S |
| | RECOMMENDATIONS. |
| | ***B) TO BE CLEAR, PROVIDE A DETAIL FOR THE UNDERGROUND |
| | INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR. |
| | PLEASE REFER TO THE SCHIER GB-75 INSTALLATION GUIDE |
| | PAGE 3, 8, 9 AND 10 OF 10 FOR DETAILS. PLEASE NOTE THE |
| | REFERENCE TO TIE DOWNS AND MAKE A FINAL DETERMINATION |
| | AS TO THE APPLICABILITY TO THIS PROJECT. |
| | ***C) PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF |
| | EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE |
| | FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. |
| | |
| | 4.NEW COMMENT: REGARDING THE SAMPLING POINT INSTALLED |
| | UPSTREAM OF THE GB-75; |
| | ***A) IN ACCORDANCE WITH THE SCHIER SV-10 INSTALLATION |
| | GUIDE (SEE FBC PL 301.7 AND 303.2), THE SAMPLING POINT |
| | SHALL BE DOWNSTREAM OF THE INTERCEPTOR. |
| | ***B) PER WPB FBC 107.2.1, PLEASE SPECIFY THE SAMPLING |
| | POINT DEVICE TO BE INSTALLED (SCHIER PRODUCT IS SV-10) |
| | ***C) PLEASE NOTE THAT THE JURISDICTION ACCEPTS A |
| | TWO-WAY CLEANOUT FOR USE AS A SAMPLING POINT |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |