2022-01-27 16:49:23RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080460
  
 ORIGINAL COMMENT:
 (1)- THIS BUILDING WAS FLAGGED AS AN UNSAFE BUILDING.
 ALSO, THERE IS ALSO A RED-TAG FOR FULL GUT REMODEL
 WITHOUT PERMITS. NEED TO PROVIDE AN ENGINEERING
 ANALYSIS ESTABLISHING THE STRUCTURAL ADEQUACY OF THE
 ALTERED BUILDING AND PROVIDE COMPLETE SET OF PLANS
 SHOWING ALL THE SCOPE OF WORK. PROVIDE COMPLETE SET OF
 PLANS SHOWING ALL THE STRUCTURAL DETAILS AND
 SPECIFICATIONS. COMPLETE PLANS WITH ALL ROOMS
 DIMENSIONS, ETC.
 PLANS NEED TO BE SIGNED AND SEALED BY THE REGISTERED
 DESIGN PROFESSIONAL AS REQUIRED BY SEC. 907
 FBC-EXISTING BUILDING.
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 907 FBC-EXISTING BUILDING. SEC. 901.2 FBC-EXISTING
 BUILDING. SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 RESPONSE:
 (1)(A)WALL SECTION DETAIL 4/A-1 ON SHEET A-0 SUBMITTED
 NEEDS TO BE REVISED:
 1-WALL SECTION SHOWS ONLY ONE TOP PLATE. THIS IS AN
 EXTERIOR BEARING WALL. TYPICALLY, WOOD FRAME BEARING
 WALLS HAVE DOUBLE TOP PLATE. ENGINEER TO REVISE DETAIL
 OR PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING WHY
 ONLY ONE TOP PLATE IS ADEQUATE. SEC. R301.1
 FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2-WALL SECTION DOESN'T SHOW THE LOAD PATH SHOWING HOW
 THE LOADS ARE TRANSFERED FROM THE ROOF TO THE
 FOUNDATION TO SHOW COMPLIANCE WITH FBC-RESIDENTIAL
 (2020). ENGINEER FAILED TO SPECIFY THE ROOF TO WALL
 HURRICANE CONNECTION, 2X4 STUDS TOP AND BOTTOM
 HURRICANE CONNECTIONS AND 2X4 STUDS SPACING.
 SEC. R601.2 FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 3- BASED ON ENGINEER'S STRUCTURAL INSPECTION REPORT
 SUBMITTED, THERE ARE NO "EXISTING WOOD TRUSSES" IN THIS
 HOUSE. PHOTOS SUBMITTED SHOW CONVENTIONAL ROOF JOISTS
 AND ROOF RIDGE CONSTRUCTION. REVISE DETAIL AS REQUIRED
 TO MATCH ACTUAL CONDITIONS. AND, ENGINEER TO PROVIDE
 HURRICANE CONNECTION OF ROOF JOIST TO ROOF RIDGE. SEC.
 R601.2 FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 (1)(B)ENGINEER'S STRUCTURAL REPORT STATES ON THE FRONT
 PAGE CONCLUSIONS& RECOMMENDATIONS THAT THE HOME DOESN'T
 HAVE ANY STRUCTURAL DEFICIENCIES AND THE HOME IS
 SUITABLE FOR ITS INTENDED OCCUPANCY. THE PHOTOS OF THE
 EXTERIOR WALL AND THE ROOF SHOWN ON THE SAME REPORT
 DON'T SHOW ANY HURRICANE STRUCTURAL CONNECTIONS BETWEEN
 THE STRUCTURAL FRAMING MEMBERS SHOWING THE LOAD PATH.
 ALSO, THE EXTERIOR WALL PHOTO SHOWS NO BASE PLATE AT
 THE BOTTOM OF THE WALL BEARING WOOD STUDS. ENGINEER OF
 RECORD TO CLARIFY AND PROVIDE COMPLETE ANALYSIS SHOWING
 HOW THIS STRUCTURE IS STRUCTURALLY SOUND TO RESIST ALL
 LOADS, INCLUDING WINDLOADS. SEC. R301.2.1
 FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 (1)(C)DELETE FASTENING SCHEDULE TABLE R602.3(1) SOWN ON
 SHEET A-0. THIS TABLE NO LONGER EXIST ON CURRENT CODE
 FBC-RESIDENTIAL(2020).
  
  
 NOTE:
 BASED ON PHOTOS SHOWN ON THE ENGINEER'S STRUCTURAL
 INSPECTION REPORT SUBMITTED, THE EXTERIOR WALL DOESN'T
 HAVE STRUCTURAL ANY STRAPS AND THERE IS NO BOTTOM
 PLATE. CONNECTIONS WILL NEED TO BE INSPECTED ONCE
 ENGINEER OF RECORD CLARIFIES CONNECTIONS
 AND PERMIT IS ISSUED.
 SAME COMMENT APPLIES TO ROOF JOISTS TO ROOF RIDGE
 CONNECTIONS.
  
 (2)- OK.
  
 ORIGINAL COMMENT:
 (3)- DESIGN PROFESSIONAL OF RECORD TO SPECIFY ROOF
 SHEATHING NAIL TYPE, SIZE AND SPACING AS REQUIRED BY
 SEC. R803.2 FBC-RESIDENTIAL.
 NOTE: SPECIFICATIONS SUBMITTED ARE INCORRECT.
  
 RESPONSE:
 DESIGN PROFESSIONAL TO REVISE SPECIFICATIONS ON SHEET
 A-0.
 REVISE ROOF SHEATHING NAILING TYPE, SIZE AND SPACING.
 NEED TO USE RING SHANK NAILS AND ROOF SHEATHING NEEDS
 TO BE NAILED WITH AT 4 INCHES O.C. IN THE FIELD AND
 EDGES AS REQUIRED BY SEC. R803.2.3.1 AND TABLE
 R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS ON ALL PLANS AND WALL
 SECTIONS TO AVOID CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 (4)- WINDOW REPLACEMENT: SPECIFY SIZE AND TYPE OF
 EXISTING WINDOW AND SIZE AND TYPE OF PROPOSED WINDOWS
 TO VERIFY COMPLIANCE WITH THE BEDROOM EGRESS
 REQUIREMENTS OF SEC. 702.5 FBC-EXISTING BUILDING.
  
 RESPONSE:
 NONE OF THE BEDROOM WINDOWS SHOWN ON SHEET A-0 COMPLY
 WITH THE EMERGENCY ESCAPE WINDOW REQUIREMENTS. EACH
 BEDROOM NEEDS TO HAVE AT LEAST ONE WINDOW OR ESCAPE
 OPENING COMPLYING WITH THIS CODE SECTION. REVISE AS
 REQUIRED.
 NOTE: ORIGINAL HOUSE HAD ONLY ONE BEDROOM. THIS HOUSE
 WAS GUTTED AND LAYOUT IS NEW. BEDROOM WINDOWS NEED TO
 COMPLY. LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING
 BUILDING. SEC. 907 FBC-EXISTING BUILDING. SEC. 901.2
 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE.
  
 (5)- OK.
 (6)- OK.
 (7)- OK.
  
 ORIGINAL COMMENT:
 (8)- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR
 PROVIDE COPY OF SIGNED CONTRACTS INCLUDING DESIGN
 PROFESSIONAL FEES.
  
 RESPONSE:
 TOTAL VALUE OF $23,200 IS TOO LOW FOR ALL THE SCOPE OF
 WORK SHOWN ON PLANS. REVISE VALUE TO REFLECT ACTUAL
 INDUSTRY COSTS FOR ALL LABOR, MATERIALS AND DESIGN
 PROFESSIONAL FEES. OTHERWISE, VALUATION WILL BE
 ESTIMATED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]