| 2021-10-27 14:10:13 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21080460 |
| | |
| | (1)- THIS BUILDING WAS FLAGGED AS AN UNSAFE BUILDING. |
| | ALSO, THERE IS ALSO A RED-TAG FOR FULL GUT REMODEL |
| | WITHOUT PERMITS. NEED TO PROVIDE AN ENGINEERING |
| | ANALYSIS ESTABLISHING THE STRUCTURAL ADEQUACY OF THE |
| | ALTERED BUILDING AND PROVIDE COMPLETE SET OF PLANS |
| | SHOWING ALL THE SCOPE OF WORK. PROVIDE COMPLETE SET OF |
| | PLANS SHOWING ALL THE STRUCTURAL DETAILS AND |
| | SPECIFICATIONS. COMPLETE PLANS WITH ALL ROOMS |
| | DIMENSIONS, ETC. |
| | PLANS NEED TO BE SIGNED AND SEALED BY THE REGISTERED |
| | DESIGN PROFESSIONAL AS REQUIRED BY SEC. 907 |
| | FBC-EXISTING BUILDING. |
| | LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| | SEC. 907 FBC-EXISTING BUILDING. SEC. 901.2 FBC-EXISTING |
| | BUILDING. SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | (2)- ROOFING WORK: |
| | (A) NEED SEPARATE ROOFING SUB-PERMIT APPLICATION. SEC. |
| | 105.1 CITY AMENDMENTS. |
| | |
| | (B) FLAT ROOF NOA 16-1206.02 SUBMITTED: SELECTED SYSTEM |
| | ON PAGE 17 OF 18 DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ALL ROOF ZONES. SEC. R301.2.1 FBC-RESIDENTIAL. NEED TO |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA. |
| | |
| | (C)PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH |
| | THE NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| | SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| | NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| | FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| | PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001 |
| | |
| | (3)- DESIGN PROFESSIONAL OF RECORD TO SPECIFY ROOF |
| | SHEATHING NAIL TYPE, SIZE AND SPACING AS REQUIRED BY |
| | SEC. R803.2 FBC-RESIDENTIAL. |
| | NOTE: SPECIFICATIONS SUBMITTED ARE INCORRECT. |
| | |
| | (4)- WINDOW REPLACEMENT: SPECIFY SIZE AND TYPE OF |
| | EXISTING WINDOW AND SIZE AND TYPE OF PROPOSED WINDOWS |
| | TO VERIFY COMPLIANCE WITH THE BEDROOM EGRESS |
| | REQUIREMENTS OF SEC. 702.5 FBC-EXISTING BUILDING. |
| | |
| | (5)-PROVIDE ALL THE WIND DESIGN CRITERIA AS REQUIRED BY |
| | SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE ULTIMATE AND |
| | NOMINAL WIND LOAD, BUILDING EXPOSURE, BUILDING MEAN |
| | ROOF HEIGHT. ALSO, SPECIFY THE COMPONENTS AND CLADDING |
| | DESIGN PRESSURES FOR DOORS AND WINDOWS. |
| | NOTE: INFORMATION SUBMITTED IS INCORRECT. |
| | |
| | (6)- SHUTTERS PRODUCT APPROVAL SUBMITTED: NEED TO |
| | PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS |
| | REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE. |
| | SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED. |
| | ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE |
| | REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | (7)- PRODUCT APPROVALS: DESIGNER OF RECORD TO REVIEW |
| | AND APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL L |
| | PRODUCT APPROVALS SUBMITTED AS REQUIRED BY SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | (8)- VALUATION DECLARED IN THE PERMIT APPLICATION IS |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR |
| | PROVIDE COPY OF SIGNED CONTRACTS INCLUDING DESIGN |
| | PROFESSIONAL FEES. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |