2021-09-24 16:10:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD REVIEW, COMMENTS NOT ADDRESSED:
  
 1. REVISE PLAN TO STATE WHAT TYPE OF FLOORING IS
 PROPOSED; THIS INFORMATION IS REQUIRED TO REVIEW
 UNDERLAYMENT.
  
 NOTE THAT THIS BUILDING HAS A 7" SLAB, SO YOU CANNOT
 USE A PRODUCT THAT WAS TESTED WITH AN 8" SLAB.
  
 2. FOR THE FLOORING UNDERLAYMENTPROVIDE THE FOLLOWING
 TEST REPORTS. NOTE THAT MAXXIM SIM 90 SPEC SHEET WAS
 SUBMITTED 2ND REVIEW, PROFLEX MSC90 SPEC SHEET
 SUBMITTED FIRST REVIEW.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 NEW COMMENT:
  
 3. SCOPE NOT CLEAR. APPLICATION IS FOR "FLOORING".
 FLOOR PLAN SHOWS A TUB. A DETAIL FOR A SHOWER WAS
 SUBMITTED. REVISE THE PLAN TO CLEARLY DEPICT ALL WORK
 PROPOSED FBC 107.
  
  
  
  