| 2021-09-01 13:20:16 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21080420 |
| | ADD: 600 OKEECHOBEE BLVD. |
| | CONT: AWNINGS OF HOLLYWOOD, INC. |
| | TEL: 954-963-7717 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. SEPT. 01/2021 |
| | ACTION: DENIED |
| | 1) THE SITE PLAN AOH1 DOES NOT INDICATE WHERE THE |
| | RETRACTABLE ROOF SYSTEM IS TO BE INSTALLED. THE PERMIT |
| | APPLICATION STATES AT THE MANOR RESTAURANT NOT MARKED |
| | ON THE PLAN. IT IS NOT CLEAR AS IF THE RETRACTABLE ROOF |
| | SYSTEM IS OVER THE FIRE PIT AREA OR WHERE THE FABRIC |
| | CANOPY OVER THE BAR TERRACE. SHEET AOH12 SHOWS WHAT |
| | APPEARS TO BE THE OUTSIDE BAR AREA BUT THE INTERIOR OF |
| | THE BUILDING IS NOT IDENTIFIED THE LAYOUT LOOKS |
| | BACKWARDS? 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 2) SHEET AOH13 IN THE LEFT HAND CORNER SHOWS 2 FOOTINGS |
| | ONE 2FEET WIDE THE OTHER 2FEET 6 INCHES WIDE JUST TO |
| | THE RIGHT DETAIL B1-2 INDICATING AN UPPER AND LOWER MAT |
| | OF STEEL RE-BAR, THE SIZE NOR SPACING IS GIVEN. |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET AOH12 SHOWS F1 & F2 FOOTINGS WITH THE COLUMNS |
| | OFF CENTER PLEASE PROVIDE PLEASE INDICATE HOW CLOSE TO |
| | THE EDGE OF THE CONCRETE FOOTING THE ? INCH X 4 INCH |
| | REDHEAD TRUBOLTS WEDGE ANCHORS ARE TO BE INSTALLED, |
| | CONCERNED WITH SHEERING OF THE CONCRETE BEING TO CLOSE |
| | TO THE EDGE. 107.2.1.2. PLEASE PROVIDE MANUFACTURES |
| | SPEC. |
| | |
| | 4) COMPLIED SHEET AOH16. SHEET AOH14 SHOW THE FABRIC ON |
| | THE RETRACTABLE SYSTEM AS FERRARI V2 FABRIC. PLEASE |
| | PROVIDE COMPLIANCE WITH THE 2020 FBC-BUILDING CODE |
| | SECTION 3105.3.4.1. FABRIC COVERED FRAMES SHALL MEET |
| | THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 |
| | OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723. |
| | |
| | 5) SHEET AOH8 SHOWS AS DOES OTHER SHEETS BOLTED |
| | CONNECTIONS, PLEASE SHOW COMPLIANCE WITH WELDED OR |
| | BOLTED CONNECTIONS |
| | THIS BUILDING CONTAINS EITHER BOLTED AND OR WELDED |
| | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 6) CALCULATIONS- DESIGN WIND LOADING CANOPY PAGE 2/32 |
| | THE V= 45MPH. PLEASE PROVIDE HOW COMPLIANCE IS MET FOR |
| | SECTION 3105.4 DESIGN. IT WOULD APPEAR THAT THE 45MPH |
| | DOES NOT MEET ANY OF THE WIND DESIGN CRITERIA. |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| | WORKING FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |