| 2021-09-13 14:22:33 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTE: STATE EXPOSURE AND RISK CATEGORY OF STRUCTURE. |
| | |
| | 1. PROVIDE DESIGN WIND LOADS PER FBC RES CHAPT 3. |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | -OR- |
| | |
| | ASCE 7-16 (VULT 170MPH 3 SEC GUST / VASD 132MPH) |
| | |
| | 2. PROVIDE STRUCTURAL PLANS FOR THE PROPOSED ENCLOSURE. |
| | |
| | 2A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON |
| | GRADE/REINFORCING/TIE DOWNS |
| | 2B) PROVIDE BUILDING PLANS WITH REQUIRED DIMENSIONS |
| | 2C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION |
| | CONNECTION DETAIL - OPTIONAL |
| | 2D) PROVIDE A WALL PLAN WITH WALL TO FLOOR CONNECTION |
| | DETAIL |
| | 2E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL |
| | CONNECTION DETAIL - OPEN TRELLIS TYPE ROOF |
| | |
| | 3. PROVIDE A CONNECTOR SCHEDULE WITH REQUIRED FASTENERS |
| | BASED ON DESIGN WIND LOADS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |