Plan Review Notes
Plan Review Notes For Permit 21080362
Permit Number 21080362
Review Stop M
Sequence Number 3
Notes
Date Text
2021-09-22 14:02:113RD REVIEW FBC-2020 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE COMMENT (1) OF PREVIOUS REVIEW CYCLE
 COMMENT: SHEET M-003: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON EACH USE OF SPACE ACCORDING TO
 FBC M 403.3.1.1 AND TABLE 403.3.1.1
 403.3.1.1.1 ZONE OUTDOOR AIRFLOW. THE MINIMUM OUTDOOR
 AIRFLOW REQUIRED TO BE SUPPLIED TO EACH ZONE SHALL BE
 DETERMINED AS A FUNCTION OF OCCUPANCY CLASSIFICATION
 AND SPACE AIR DISTRIBUTION EFFECTIVENESS IN ACCORDANCE
 WITH SECTIONS 403.3.1.1.1.1 THROUGH 403.3.1.1.1.3.
  
 VBZ = RPPZ + RAAZ (EQUATION 4-1)
  
 WHERE:
 AZ = ZONE FLOOR AREA: THE NET OCCUPIABLE FLOOR
 AREA OF THE SPACE OR SPACES IN THE ZONE.
 PZ = ZONE POPULATION: THE NUMBER OF PEOPLE IN
 THE SPACE OR SPACES IN THE ZONE.
 RP = PEOPLE OUTDOOR AIR RATE: THE OUTDOOR
 AIRFLOW RATE REQUIRED PER PERSON FROM
 TABLE 403.3.1.1.
 RA = AREA OUTDOOR AIR RATE: THE OUTDOOR AIRFLOW
 RATE REQUIRED PER UNIT AREA FROM TABLE
 403.3.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  