| 2021-09-22 14:02:11 | 3RD REVIEW FBC-2020 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SEE COMMENT (1) OF PREVIOUS REVIEW CYCLE |
| | COMMENT: SHEET M-003: PLEASE PROVIDE THE OUTDOOR AIR |
| | CALCULATIONS BASED ON EACH USE OF SPACE ACCORDING TO |
| | FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| | 403.3.1.1.1 ZONE OUTDOOR AIRFLOW. THE MINIMUM OUTDOOR |
| | AIRFLOW REQUIRED TO BE SUPPLIED TO EACH ZONE SHALL BE |
| | DETERMINED AS A FUNCTION OF OCCUPANCY CLASSIFICATION |
| | AND SPACE AIR DISTRIBUTION EFFECTIVENESS IN ACCORDANCE |
| | WITH SECTIONS 403.3.1.1.1.1 THROUGH 403.3.1.1.1.3. |
| | |
| | VBZ = RPPZ + RAAZ (EQUATION 4-1) |
| | |
| | WHERE: |
| | AZ = ZONE FLOOR AREA: THE NET OCCUPIABLE FLOOR |
| | AREA OF THE SPACE OR SPACES IN THE ZONE. |
| | PZ = ZONE POPULATION: THE NUMBER OF PEOPLE IN |
| | THE SPACE OR SPACES IN THE ZONE. |
| | RP = PEOPLE OUTDOOR AIR RATE: THE OUTDOOR |
| | AIRFLOW RATE REQUIRED PER PERSON FROM |
| | TABLE 403.3.1.1. |
| | RA = AREA OUTDOOR AIR RATE: THE OUTDOOR AIRFLOW |
| | RATE REQUIRED PER UNIT AREA FROM TABLE |
| | 403.3.1.1. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |