| 2021-09-22 09:14:14 | OFFICE BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING G-001 SHOWS AN 18" GRAB BAR ABOVE THE | | | REQUIRED 42 INCH GRAB BAR ON THE SIDE OF THE TOILET - | | | PLEASE SHOW THE REQUIRED 12 INCH CLEARANCE ABOVE THE | | | REQUIRED 42 INCH TOILET SIDE GRAB BAR AND ANYTHING | | | ABOVE THE GRAB BAR - THE 18 INCH GRAB BAR IS NOT A | | | REQUIREMENT OF THE 2020 FBC ACCESSIBILITY CODE - FBC | | | ACCESSIBILITY 609.3 THE SPACE BETWEEN THE GRAB BAR AND | | | PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305 MM) | | | MINIMUM. | | | | | | | | | | | | | | | |
|