Plan Review Notes
Plan Review Notes For Permit 21080362
Permit Number 21080362
Review Stop P
Sequence Number 2
Notes
Date Text
2021-08-31 14:32:3708/31/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET G-001, SOME HEIGHTS FOR ACCESSIBILITY NEED
 TO BE ADJUSTED FOR THE TYPICAL MOUNTING HEIGHTS;
  
 A. THE GRAB BAR ON THE BACK THE SIX INCHES, NOT
 REQUIRED AS THE TOILET MAY BE ONE FOOT FOUR INCHES TO
 ONE FOOT SIX INCHES PER THE 20230 FBC SEC. 604.2
 LOCATION.
  
 B. THE GRAB BAR FROM THE SIDE FROM THE BACK CALLS FOR
 12 INCHES PER THE 2020 FBC SEC. 604.5.1 SIDE WALL.
  
 C. GRAB BAR FOR THE SIDEWALL IS INSTALLED IN A VERTICAL
 POSITION AND SHALL BE INSTALLED IN A HORIZONTAL
 POSITION PER THE 2020 FBC ACC SEC. 609.4.
  
 D. THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE 40
 INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC.
 603.3.
  
 2. ON SHEET A100, THERE SEEMS TO BE A SINK; IS IT A
 BREAK ROOM? IF SO, CAN YOU PLEASE LABEL IT AND SHOW THE
 DETAIL AND LABEL IT AS WELL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. ON SHEET A101, THERE SEEMS TO BE A SINK; IS IT A
 BREAK ROOM? IF SO, CAN YOU PLEASE LABEL IT AND SHOW THE
 DETAIL AND LABEL IT AS WELL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. ON SHEET A400;
  
 A. ON DETAIL 1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE AND DIMENSIONS IN FROM OF THE SINK PER THE 2020
 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 B. ON DETAIL 2, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE AND DIMENSIONS OF THE SINK PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 C. ON DETAIL 4, IT LOOKS LIKE THIS RESTROOM IS AN
 ACCESSIBLE RESTROOM. IF SO WOULD YOU, PLEASE LABEL AND
 SHOW THE CLEAR FLOOR SPACE FOR THE LABORATORY PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. ON DETAIL 10, THE GRAB BAR SHALL BE A MINIMUM OF 42
 INCHES AND NOT SHOWN. WOULD YOU PLEASE SHOW PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. ON THAT SAME DETAIL, IT SHOWS THE CENTER GRAB BARS,
 AND THEY SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE PER THE 2017 FBC ACC SEC. 609.4.
  
 F. ON DETAIL 14, THE CENTER OF THE TOILET IS NOT SHOWN.
 WOULD YOU PLEASE PROVIDE PER THE 2020 FBC SEC. 604.2
 LOCATION. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE
 SIDEWALL OR PARTITION.
  
 G. ON THAT SAME DETAIL, IT DOES NOT SHOW THE DIMENSION
 HEIGHT OF THE MIRROR 40 INCHES TO THE BOTTOM OF THE
 REFLECTIVE, BOTTOM OF LAV 27 INCHES, GRAB BARS TO THE
 TOP OF THE GRIPPING SURFACE AT 36 INCHES. THE GRAB BAR
 FROM THE WALL, THE SIX INCHES IS NOT ACCURATE DUE TO
 THE DEVIANCE OF THE TOILET; IT SHOULD BE PER FIGURE
 604.5.2 REAR WALL GRAB BAR WATER CLOSETS.
  
 I. ON DETAIL 15 AND 21, THE GRAB BAR ON THE REAR SHOW
 BE AS FIGURE 604.5.2 REAR WALL GRAB BAR WATER CLOSETS.
 SHOW THE DIMENSION HEIGHT OF THE MIRROR 40 INCHES TO
 THE BOTTOM OF THE REFLECTIVE. THE BOTTOM OF THE LAV
 NEEDS TO SHOW 27 INCHES.
  
 J. ON THAT SAME DETAIL, THE PARTITION HEIGHT IS NOT
 GREATER THAN 12 INCHES FROM THE FINISHED FLOOR SURFACE
 PER THE 2020 FBC P 405.3.5 URINAL PARTITIONS.
  
 K. ON DETAIL 16, THE GRAB BAR NEEDS TO BE A MIN OF 42
 INCHES WHICH IS NOT SHOWN PER THE 2020 FBC ACC SEC.
 604.5.1 SIDE WALL. THE BOTTOM OF THE LAV MUST BE 27
 INCHES, GRAB BARS TO THE TOP OF THE GRIPPING SURFACE AT
 36 INCHES, AND MIRROR 40 INCHES TO THE BOTTOM OF THE
 REFLECTIVE.
  
 M. WOULD YOU PLEASE SHOW OR MENTION THAT THE LAVATORY
 WATER SUPPLY AND DRAINPIPES UNDER THE SIDE SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 N. ON DETAIL 20, PLEASE PROVIDE THE 60 INCHES OF THE
 TURNING RADIUS IN BOTH ACCESSIBLE RESTROOMS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 O. ON THAT SAME DETAIL, THE 30 INCHES BY 48 INCHES ON
 THE LAV IN THE TWO-STALL IS MISSING, AND THE URINAL
 CLEAR FLOOR SPACE AND DIMENSION IN THE MEN'S DOES IS
 NOT SHOWN. THE TWO LAVS IN THE OPEN AREA REQUIRE
 DIMENSION AND THE CLEAR FLOOR SPACE.
  
 P. DOOR HANDLE FOR STALLS HARDWARE SHOULD BE NOTED ON
 BOTH SIDES OF THE DOOR PER THE 2020 FBC ACC SEC.
 404.2.7.
  
 Q. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
  
 R. HANDICAP HI AND LO WATER FOUNTAIN MISSING A HEIGHT
 DETAIL AND THE CLEAR FLOOR SPACE WITH THE DIMENSIONS
 PER WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 S. THERE IS A SINK DETAIL MISSING ON THE 12TH-FLOOR
 NEST TO THE LOCATION SUITE 1259B. IT IS NOT IN ANY OF
 THE DETAILS, AND IF IT'S ACCESSIBLE, PLEASE SHOW IT AS
 WELL. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 5. ON SHEET P-003, UNDER THE ICE MAKER IN FIXTURE
 SCHEDULE, THE ICEMAKER AND COFFEE MAKER SHALL BE
 EQUIPPED WITH AN IN-LINE VACUUM BREAKER THAT COMPLIES
 WITH ASSE 1024 PER THE 2020 FBC SEC. 608.13.10. THE
 BACKFLOW PREVENTER MENTION 1022 IS FOR A SODA MACHINE,
 AND IF ONE IS PROVIDED, IT WILL REQUIRE A DRAIN AS THEY
 SPIT WATER PER MANUFACTURES SPECIFICATIONS.
  
 6. ON SHEET P-501 DETAIL 8, THE TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3 PER THE 2017 FBC SEC. 416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
  
  
 7. ON SHEET P- 502;
  
 A. ON DETAIL FOR THE WATER HEATER, PLEASE SHOW A VALVE
 DIRECTLY BEHIND AS IT SHOWS IN FRONT OF THE
 RECIRCULATING PUMP PER MOST MANUFACTURERS
 SPECIFICATIONS.
  
 B. ON THAT SAME DETAIL, IT SHOWS THE DRAIN VALVE
 CONNECTED TO THE DRAIN FOR THE DRAIN PAN. PLEASE
 SEPARATE AND HAVE DRAIN DUMP INTO THE PAN PER THE 2020
 FBC P 501.3
  
 8. ON SHEET P-601;
  
 A. THE ISOMETRIC SANITARY IS HARD TO FOLLOW, THE LINE
 PATTERNS MAY BE TOO THICK, AND NO FIXTURES ARE LABELED.
 IF POSSIBLE, ENLARGE AND MAKE CLEAR TO READ, SHOW TRAP
 PRIMERS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THERE SEEM TO BE A P-TRAP NEXT TO THE FLOOR DRAIN IN
 CONF. R, 1252, BUT IT IS AN FD-X, AND IT'S NOT LABELED.
 IT LOOKS LIKE IT'S ON THE WRONG LEVEL AND HARD TO
 UNDERSTAND. WOULD YOU PLEASE CORRECT OR MOVE FOR
 CLARITY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN THE WOMEN'S AND MEN'S ROOMS, THE LAVS FOR THE
 ACCESSIBLE STALLS ARE NOT SHOWN TO THE CONNECTION FOR
 SANITARY. WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. ON THAT SAME SHEET FOR THE WATER ISOMETRIC LABEL,
 SHUT OFF VALVES, SHOW TRAP PRIMERS, AND AIR ARRESTORS.
 IF POSSIBLE, DO THE SAME FOR LINE PATTERNS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 ON THE RECIRCULATING PUMP, PLEASE REFER TO THE MANIFOLD
 FOR THE HOT WATER LINES WHICH SHALL BE SUPPLIED TO THE
 SOURCE; PLEASE REFER TO THE 2020 FBC ENERGY CODE TABLE
 C404.5.1. MAXIMUM ALLOWABLE PIPE LENGTH METHOD. THERE
 SEEMS NOT TO BE A LOOP.
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETINGS IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  