Plan Review Notes
Plan Review Notes For Permit 21080362
Permit Number 21080362
Review Stop M
Sequence Number 2
Notes
Date Text
2021-08-27 16:44:441ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080362
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-003: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON EACH USE OF SPACE ACCORDING TO
 FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 2) PLEASE SHOW THE REQUIRED PROTECTION WHERE THE DUCT
 SYSTEM PENETRATES THE RATED WALLS ON BOTH FLOORS. FBC
 M607
  
 3) PLEASE SHOW A DETAIL OF THE RETURN AIR PATH FROM
 TENANT SPACE BACK TO THE RETURN AIR DUCT FROM THE CORE
 MECHANICAL SYSTEM ON EACH FLOOR. FBC M 601.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  