2021-08-31 11:51:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE EP-211, EP-212
  
 OUTLETS INSTALLED SHALL BE INSTALLED PER 406.12(5)
  
 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND
 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE
 RECEPTACLES IN THE AREAS
 SPECIFIED IN 406.12(1) THROUGH (7) SHALL BE LISTED
 TAMPERRESISTANT RECEPTACLES.
 (1) DWELLING UNITS IN ALL AREAS SPECIFIED IN 210.52 AND
 550.13
 (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS
 (3) CHILD CARE FACILITIES
 (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES
 (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE
 LIKE IN CLINICS, MEDICAL AND DENTAL OFFICES AND
 OUTPATIENT FACILITIES
 (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2
 TO INCLUDE PLACES OF WAITING TRANSPORTATION,
 GYMNASIUMS, SKATING RINKS, AND AUDITORIUMS
 (7) DORMITORIES
  
 PAGE EP-212
  
 CONFERENCE ROOMS 1250,1251,1254, 1255 WALL AND FLOOR
 OUTLETS SHALL BE INSTALLED PER 210.71(A)(B).
  
 210.71 MEETING ROOMS.
 (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2
 (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE
 OUTLETS FOR
 NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE
 RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.71(B)
 (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF
 RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN
 FIXED FURNITURE, SHALL NOT BE LESS THAN AS DETERMINED
 IN (1) AND (2). THESE RECEPTACLE OUTLETS SHALL BE
 PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2
 (215 FT2) SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 LOCATED IN THE FLOOR AT A DISTANCE NOT LESS THAN 1.8 M
 (6 FT) FROM ANY FIXED WALL
 FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR
 SPACE.
  
  