Plan Review Notes
Plan Review Notes For Permit 21080353
Permit Number 21080353
Review Stop G
Sequence Number 1
Notes
Date Text
2021-08-26 11:30:5008/26/2 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE HAVE A SIGNATURE ON THE ISOMETRIC
 DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL.
  
 2. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 3. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF
 THE DELIVERY GAS METER TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER THE 2020 FBC RES. SEC.
 G2413.4.1.
  
 4. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL
 BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING
 EHD NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. WOULD YOU PLEASE PROVIDE THE SIZING TABLE OR NOTE
 THE PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. WOULD YOU PLEASE SUBMIT THE MANUFACTURERES
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES.
 SEC.G2408.1.
  
 8. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC FG SECS. 402.2 AND 301.3.
  
 9. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT
 OF REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC
 RES. SEC G2421.2?
  
 10. WOULD YOU PLEASE SHOW AND LABEL THE SHUT-OFF, AND
 THEY SHALL BE ACCESSIBLE WITHOUT MOVING THE EQUIPMENT
 PER THE 2020 FBC SEC. G2403 (202) GD, ACCESS.
  
 11. WOULD YOU PLEASE SHOW AND LABEL ALL DRIP LEGS ON
 EQUIPMENT EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD
 GRILLS PER THE 2020 FBC RES. SEC. G2419.2.
  
 12. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS? REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1 OR 410.1.
  
 13. ALL THE BTU LOADS OF EACH APPLIANCE ARE SHOWN.
 WOULD YOU PLEASE TOTAL BTU LOAD ON THE SYSTEM AND
 DISPLAY IT ON PLANS PER THE 2020 FBC RES. SEC. G2413.
  
 14. THE SITE PLAN SHOWS A GAS GRILL. INDICATE ON THE
 PLANS IF THE GRILL IS LOCATED UNDER A ROOF PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1. A GAS GRILL IS LABELED
 FOR OUTDOOR USE; IF IT IS UNDER A COVERED PATIO, PLEASE
 PROVIDE MANUFACTURERS RECOMMENDATION FOR A VENTILATION
 HOOD PER THE 2020 FBC RES. SEC. G2408.1
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  