| 2021-09-07 17:20:23 | 09/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. ON SHEET A-001; |
| | A. UNDER APPLICABLE CODE, IT REFERS TO THE 6TH EDITION, |
| | AND THE CURRENT IS THE 7TH EDITION. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THE ACCESSIBILITY CODE IS NOT MOTIONED UNDER THE |
| | APPLICABLE CODES. WOULD YOU PLEASE ADD IT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | C. UNDER PROJECT DESCRIPTION/SCOPE OF WORK, IT REFERS |
| | TO THE 2017 6TH EDITION FOR EXISTING AND BUILDING. |
| | WOULD YOU PLEASE CORRECT THE CURRENT 2020 7TH EDITION |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. ON SHEET A-003; |
| | |
| | A. IF POSSIBLE, WOULD YOU PLEASE DELETE OR |
| | STRIKETHROUGH ANY ADA DETAILS NOT PERTAINING TO THIS |
| | PROJECT TO MINIMIZE CONFUSION IN THE FIELD INSTALLATION |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. ON THE BOTTOM OF THE PAGE, LETTER B HAS THE GRAB BAR |
| | 6 INCHES FROM THE WALL, WHICH IS INCORRECT AS THE |
| | TOILET MAYBE 16 INCHES TO 18 INCHES FROM THE WALL PER |
| | THE 2020 FBC ACC. SEC. 604.2 LOCATION. WOULD YOU PLEASE |
| | REFER TO THE 2020 FBC ACC 604.5.2 REAR WALL? |
| | |
| | C. ON A AND B, THE GRAB BAR IS MEASURED TO CENTER AND |
| | SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE |
| | PER THE 2020 FBC ACC SEC. 609.4. |
| | |
| | D. ON THE ADA GUIDELINES FOR THE RESTROOM, THE TOILET, |
| | AND GRAB BAR SIZES ARE INCORRECT. THE TOILET PAPER IS |
| | WRONG TO SEE 2020 FBC ACC SEC. 604.7, THE BACK GRAB BAR |
| | IS INCORRECT TO SEE 2020 FBC ACC SEC. 604.5.2 REAR |
| | WALL, THE DISTANCE FROM THE SIDE ALL VARIES SEE 2020 |
| | FBC ACC. SEC. 604.2 LOCATION, THE TOP OF THE LAV IS NOT |
| | SHOWN SEE AND THE HIGHT OF THE GRAB BARS ARE INCORRECT, |
| | SEE 2020 FBC ACC SEC. 609.4. |
| | |
| | E. WOULD YOU PLEASE SHOW THE HANDLE OF THE WATER CLOSET |
| | TO THE OPEN SIDE PER THE 2020 FBC ACC SEC. 604.9.5. |
| | |
| | F. SEAT NEEDS TO BE OPEN FRONT, 2020 FBC P 420.3 WATER |
| | CLOSET SEATS. |
| | |
| | G. THE TOILET PAPER DISPENSERS SHALL BE 7? INCHES |
| | MINIMUM AND 9? INCHES MAXIMUM IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER PER |
| | THE 2020 FBC ACC SEC. 604.7. |
| | |
| | H. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | I. WOULD YOU PLEASE SHOW THE RESTROOM WITH THE LAV AND |
| | TOILET ALONG WITH THE CLEAR FLOOR SPACE IN DIMENSIONS |
| | PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE |
| | AND 2020 FBC ACC. SEC. 604.3.1. |
| | |
| | 3. ON SHEET A-601; |
| | A. ON DETAIL 5, THE GRAB BARS SHALL BE MEASURED TO THE |
| | TOP OF THE GRIPPING SURFACE PER THE 2020 FBC ACC SEC. |
| | 609.4. |
| | |
| | B. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE PER THE 2020 FBC ACC SEC. 609.4. |
| | |
| | C. WOULD YOU PLEASE SHOW REINFORCING FOR GRAB BARS PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON DETAIL 6, IT DOESN?T SHOW THE HANDLE ON THE OPEN |
| | SIDE PER THE 2020 FBC ACC SEC. 604.9.5. THE 6 INCHES |
| | FROM THE WALL FOR THE GRAB BAR IS NOT CORRECT AS THE |
| | TOILET MAY BE 16 INCHES TO 18 INCHES FROM THE WALL PER |
| | THE 2020 FBC ACC. SEC. 604.2 LOCATION. WOULD YOU PLEASE |
| | REFER TO THE 2020 FBC ACC 604.5.2 REAR WALL? WOULD YOU |
| | PLEASE ADD THAT THE MIRROR IS MEASURED TO THE |
| | REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3. |
| | |
| | 4. ON SHEET P-2, WHERE TEMP VALVES ARE INSTALLED, THEY |
| | SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3 PER THE 2020 FBC SEC. 416.5 TEMPERED |
| | WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |