| 2021-08-30 15:58:07 | UNIT ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ACCESSIBLE RESTROOM - PLEASE SHOW MIRROR HEIGHT FROM | | | THE FINISHED FLOOR TO THE "REFLECTIVE SURFACE" PER FBC | | | A 603.3 MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER | | | DISPENSER DIMENSION FROM THE FACE OF THE TOILET PER FBC | | | A 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. | | | 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE PAPER TOWEL | | | DISPENSERS FROM THE OUTLET TO COMPLY WITH THE REACH | | | RANGES PER FBC 308 | | | 4) DRAWING S-201 SHOWS A SLAB IN FILL - PLEASE SHOW IF | | | TERMITE PROTECTION IS REQUIRED PER FBC 1816.1.2 |
|