| 2021-08-23 07:16:05 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21080310 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ADD A NOTE ON THE DRAWING STATING ALL HOODS |
| | WILL REQUIRE A SEPARATE PERMIT APPLICATION, DRAWINGS |
| | AND PLAN REVIEW. THE HOODS WILL NOT BE REVIEWED UNDER |
| | THIS PERMIT. |
| | |
| | 2) PLEASE ADD A NOTE ON THE DRAWING STATING ALL |
| | REFRIGERATION WILL REQUIRE A SEPARATE PERMIT |
| | APPLICATION, DRAWINGS AND PLAN REVIEW. THE |
| | REFRIGERATION WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE |
| | USE OF SPACE IN THIS TENANT SPACE I.E. KITCHEN, DINING, |
| | BAR, RECEPTION. FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FBC EC C403.2.1 |
| | |
| | 5) SHOW LOCATION OF THE NEW OACU-1. FBC 107.2.1 |
| | |
| | 6) PLEASE IDENTIFY THE RETURN AIR LOCATION FOR AHU-1 |
| | AND AHU-3. FBC M 601.5 (7) |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |